Checksum (CRC16)

The checksum (CRC16) is used to detect transmission errors.
If the evaluation reveals an error, the relevant device will not respond.

CRC = 0xFFF

CRC = CRC XOR ByteOfMessage
For (1 to 8)

CRC = SHR (CRC)
if (flag to the right = 1)
then
CRC = CRC XOR
0xA001

else

while (not all ByteOfMessage edited)

+

The low byte of the checksum will be transmitted first.

Data query:

Reading 2 words from address 6 (CRC16 = 0x24A0)

0B

03

00

06

00

02

A0

24

CRC16

Reply:

(CRC16 = 0x6105)

0B

03

04

00

00

42

C8

61

05

Word 1

Word 2

CRC16

The following functions for the device will be available:

Function number

Function

0x03 / 0x04

Reading n words (n

£ 12)

0x06

Writing 1 word

0x10

Writing n words (n

£ 2)