Communication sequence

Both the start and end of a data block are characterized by transmission pauses. The
maximum period of time that may elapse between 2 successive characters is 3 times
the period of time required for the transmission of one character.
The character transmission time (period of time required for the transmission of 1 char-
acter) is dependent on the Baud rate and the type of data format.

Using a data format of 8 data bits, no parity bit and 1 stop bit, the character transmis-
sion time is calculated as follows:

Character transmission time [ms] = 1000 * 9 bits / Baud rate

Data query by the master

Transmission time = n characters * 1000 * x bits / Baud rate

Identification of end of data query

3 characters * 1000 * x bits / Baud rate

Handling of data query by the slave (

£ 250 ms)

Reply by the slave

Transmission time = n characters * 1000 * x bits / Baud rate

Identification of end of reply

3 characters * 1000 * x bits / Baud rate

Identification of the data query or end of the reply with a data format of 10 / 9 bits.

Waiting time = 3 characters * 1000 * x bits / Baud rate

Baud rate

Data format [bits]

Waiting time [ms]

9.600

9

2.813

19.200

9

1.406

Process

Example

Advertising