Stoelting SC118 User Manual

Page 19

Advertising
background image

11

SECTION 5

SEQUENCE OF OPERATIONS

5.1 LIGHTS
On/Off light switch is independent of all other switches.
When on, the light transformer is operational and the lights
illuminate.

5.2 SWITCHES

On/Off/Clean

Mode

Switch

Switch

Position

Position

Sequence of Operations

Clean

Serve

-Drive Motor and Condenser Fan Motor start and run together,

or

No time limit exists.

Standby

-Power Transformer, torque switch, compressor, liquid level
control, and mix low light are non-operational.

On

Serve

-Drive Motor and Condenser Fan start and run together
continuously.
-Power Transformer is on.
-Liquid level control and mix low light are operational.
-With liquid mix or loose slush in the freezing cylinder, the torque
switch is closed. The delay-on-make timer starts the compressor
after a 10-30 second delay.
-When the slush reaches consistency, the torque switch opens
and the compressor immediately shuts off. The drive motor and
condenser fan motor continue to run.

On

Standby

-Power transformer, liquid level control and mix low light are
operational only when the temperature control is closed.
-Drive motor, condenser fan motor, and compressor cycle on and
off with the temperature control (compressor start delays 10-30
seconds).

NOTE

If the temperature control is set too cold, control will default to the torque switch to prevent freeeze-up.

5.3 SAFETY SWITCH

Door Switch - If the front door is removed, the freezer will not function.

Motor Internal Thermostat - If the motor overheats, the freezer will not function.

Warning - The motor internal thermostat automatically resets as the motor cools. The freezer will automatically

restart. Disconnect freezer from power source for servicing.

High Pressure Cutout Switch - If the compressor discharge pressure exceeds 470 PSIG, the freezer will not

function.