Specifications

Specification Value

Marley

/

Sigma Steel

Cooling Tower

/

Specifications: Base

17

6.0 Fill, Louvers and Drift Eliminators:

6.1

Fill shall be film-type, 15 mil thick,

thermoformed PVC, with louvers

formed as part of each fill sheet. Fill

shall be suspended from stainless

steel structural tubing supported from

the upper tower structure, and shall

be elevated above the floor of the cold

water basin to facilitate cleaning. Air

inlet faces of the tower shall be free of

water splash-out.

6.2

Drift eliminators shall be PVC, triple-

pass, and shall limit drift losses to

0.005% or less of the design water

flow rate.

Louvers integral with the fill keep the flowing water within the confines

of the fill. The separate external louvers used by others permit water to

escape the fill and form ice or produce an unsightly situation adjacent

to the tower. If you plan to use your tower in the wintertime, particu-

larly for free cooling, integral louvers will put your operating concerns

to rest.

Vertical blade-type eliminators, as well

as misdirected cellular types, cause

much of the fan power to be wasted

in turning the horizontal flow of air

vertical for its exit through the fan

cylinder. This power is, of course, not

available for contribution to thermal

performance.

Drift rate varies with design water

loading and air rate, as well as drift

eliminator depth and number of direc-

tional changes. A drift rate of 0.001%

is readily available in standard configuration without premium cost. If a

lower rate is required, please discuss with your Marley sales represen-

tative.

Louver

Section

Drift Eliminator

Section

Fill Section