Specification Value

Marley

/

Sigma Steel

Cooling Tower

/

Specifications: Base

19

9.2

The top of the tower shall be equipped

with a sturdy 42" high guardrail sys-

tem, complete with top rails, interme-

diate rails and toeboards, conforming

to OSHA standards. Guardrails and

posts shall consist of 1.66" O.D. x 15

gauge galvanized structural tubing.

Posts shall be spaced on centers of 8'-

0" or less.

9.3

One endwall of the tower shall be

equipped with a 20" wide aluminum

vertical ladder, through-bolted to the

endwall structure. Ladder shall rise

from the cold water basin level to the

top of the fan deck guardrail, and shall

be designed and installed in confor-

mance with OSHA standards.

10.0 Cold Water Collection Basin:

10.1 The collection basin shall be heavy-

gauge galvanized steel and shall

include the number and type of suction

connections required to accommodate

the out-flow piping system shown on

the plans. Suction connections shall be

equipped with debris screens. A fac-

tory installed, float operated, mechani-

cal make-up valve shall be included. An

overflow and drain connection shall be

provided in each cell of the tower. The

basin floor shall slope toward the drain

to allow complete flush out of debris

and silt which may accumulate.

11.0 Scope of Work:

11.1 The cooling tower manufacturer shall

be responsible for the design, fabrica-

tion, and delivery of materials to the

project site, and for the erection of

the tower over supports provided by

others. Unless otherwise specified, all

external piping, pumps, controls, and

electrical wiring will be outside the

cooling tower manufacturer's scope of

work.

tion, alerting you to a potential maintenance head-

ache.

Good maintenance practice requires period-

ic access to the top of the tower to inspect

the distribution basins, as well as the struc-

tural integrity of the fan deck, fan cylinder,

and fan — especially the fan blade secur-

ing hardware. There are no induced-draft

cooling tower designs that are immune to

this need!

For the comfort and safety of your operating personnel, the Sigma

Steel tower includes a ladder and guardrail of the quality and design

indicated — and we strongly recommend that you require it of all bid-

ders! Portable ladders and other "make-do" access means are inappro-

priate for equipment of this size and complexity.

This basic specification assumes that the tower will be erected over

a concrete basin at grade level. If the tower is to be installed on an

elevated supporting platform, the steel cold water collection basin indi-

cated on page 24 should be included in the specifications.

Please be clear in your specifications and inquiry

documents regarding the full scope of work

expected. That will help assure that your

bid comparisons will be made on as equal

a basis as possible—and will help to

avoid any misunderstandings during