Marley, Sigma steel cooling tower, Specifications: options – SPX Cooling Technologies Marley Sigma Steel User Manual

Page 26

Advertising
background image

Specifications

Specification Value

Marley

/

Sigma Steel

Cooling Tower

/

Specifications: Options

26

Low Noise Tower:

1.1

Add the following at the end of this

paragraph: The cooling tower shall be

quiet operating, and shall produce an

overall level of sound no higher than ____

dBA at the critical location indicated on

the Plans.

Sound produced by a Sigma Steel tower operating in an unobstructed

environment will meet all but the most restrictive noise limitations –

and will react favorably to natural attenuation. Where the tower has

been sized to operate within an enclosure, the enclosure itself will have

a damping effect on sound. Sound also declines with distance – by

about 5 or 6 dBA each time the distance doubles. Where noise at a

critical point is likely to exceed an acceptable limit, you have several

options – listed below in ascending order of cost impact:

• Where only a slight reduction in noise will satisfy — and the source

of concern is in a particular direction — merely turning the tower may

be the answer. Less sound emanates from the cased face of the tower

than does from the air intake face.

• In many cases, noise concerns are limited to nighttime, when ambi-

ent noise levels are lower and neighbors are trying to sleep. You can

usually resolve these situations by using two-speed motors in either

1800/900 or 1800/1200 RPM configuration; and operating the fans at

reduced speed without cycling “after hours”. (The natural nighttime

reduction in wet-bulb temperature makes this a very feasible solution

in most areas of the world, but the need to avoid cycling may cause

the cold water temperature to vary significantly.)

• Variable speed drives automatically minimize the tower's noise level

during periods of reduced load and/or reduced ambient without sacri-

ficing the system's ability to maintain a constant cold water tempera-

ture. This is a relatively inexpensive solution, and can pay for itself

quickly in reduced energy costs.

• Where noise is a concern at all times (for example, near a hospital),

the best solution is to oversize the tower so it can operate continu-

ously at reduced (1200 or 900 RPM) motor speed even at the highest

design wet-bulb temperature. Typical sound reductions are 7 dBA at

2/3 fan speed or 10 dBA at 1/2 fan speed, but larger reductions are

often possible.

• Extreme cases may require inlet and discharge sound attenuator

sections; however, the static pressure loss imposed by attenuators

may necessitate an increase in tower size. This is the least desirable

approach because of the significant cost impact – and because of the

obstruction to normal maintenance procedures.

Your Marley representative can help you meet your sound require-

ments.

Advertising