Specifications

Specification Value

Marley

/

Sigma Steel

Cooling Tower

/

Specifications: Options

25

Oil Level Sight Glass:

5.4 Replace paragraph 5.4 with the fol-

lowing: A galvanized oil gauge and

drain line shall extend from the gear

reducer to the vicinity of the motor,

and shall be equipped with a bronze-

bodied oil level sight glass.

Miscellaneous Options

Steel Cold Water Basin:

10.1 Replace paragraph 10.1 with the fol-

lowing: Include a cold water collection
basin constructed of 12 gauge hot-dip
galvanized formed steel sheets. These
sheets shall be bolted, gasketed and
caulked to form a watertight basin 18"
deep. A depressed, side outlet sump shall
be included, having a 1/4" thick faceplate
drilled for a standard 125# flange connec-
tion. An appropriately sized (3" diameter
or larger) galvanized standpipe overflow
shall be provided. The standpipe shall be
removable for flush-out cleaning of the
basin. A float-operated, mechanical make-
up valve shall also be included, installed
adjacent to the endwall access door.

Factory Mutual Approval:

3.5 Add the following paragraph in the

Construction section: The tower shall

include all design and material modi-

fications necessary to meet the fire

rating requirements of Factory Mutual.

The product proposed shall be listed in

the FM Approval Guide, latest edition.

Hot Water Basin Covers:

7.3 Add the following paragraph to

the Hot Water Distribution System

Section: The distribution basins shall

include galvanized steel covers. These

covers shall be designed for a uniform

live load of 40 psf, and shall be easily

removable for maintenance.

Air Inlet Screens:

8.3 Add the following paragraph to the

Casing Section: The air inlet faces of

the tower shall be covered by 1" mesh

hot-dip galvanized welded wire screens.

Screens shall be mounted in galvanized

steel U-edging and shall be removable.

The oil level sight glass is a convenience item that is preferred by many

users. The same purpose is, of course, served by either the dip stick or

the sight glass.

Marley basins are used to permit the installation of towers on elevated

platforms or foundations.

This is the simplest of several cold water basin designs available for

the Sigma Steel towers. Because of its bolted construction, it has the

advantage of being hot-dip galvanized after fabrication. Marley can

also install a 10 gauge welded stainless steel basin for a Stainless Steel

Sigma. See 24.

This could have a very beneficial effect

upon your fire insurance premiums.

Towers not able to meet FM require-

ments may require the inclusion of a fire

protection sprinkler system to achieve a

comparable level of insurance premium

cost.

These covers are designed to keep leaves and debris out of the circu-

lating water system. They also serve to suppress algae formation by

shielding the incoming hot water from direct sunlight.

In wooded or windy areas, these screens help to keep leaves or blow-

ing debris out of the cooling tower and circulating water system.

Advertising