Marley, Sigma steel cooling tower, Engineering data : schematic – SPX Cooling Technologies Marley Sigma Steel User Manual

Page 6

Advertising
background image

Marley

/

Sigma Steel

Cooling Tower

/

Engineering Data : Schematic

6

Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.

The UPDATE web-based selection software
—available at spxcooling.com—provides
Sigma Steel model recommendations based
on customer's specific design requirements.

A

BAYS AT 4'-0" =

L

C

DIAMETER FAN

4

1

/

2

"

4

1

/

2

"

COLUMN

COLUMN

CL

CL

COLUMN

CL

W

OUT

-T

O-OUT OF T

OWER

NOTE

1 Use this bulletin for preliminary layouts only. Obtain cur-

rent drawings from your Marley sales representative.

2 Last number of model indicates number of cells. Change as

appropriate for your selection. Primary engineering data is per

cell.

3 Height shown is from base of tower columns to top of fan

cylinder.

4 Pumping head shown is from base of tower columns.

H

B

TOP OF

FAN CYLINDER

BASE OF

TOWER COLUMNS

FAN DECK

13'-1

1

/

8

"

Tower

Model

GPM

per cell

Dimensions

Maximum

Motor hp

Average

Pumping

Head

W

L

H

A

B

C

121-111

500-4500

25'-4"

12'-0"

19'-1

1

8

"

3

6'-0"

120"

60

17.3'

122-111

650-6000

27'-4"

16'-0"

19'-1

1

8

"

4

6'-0"

144"

60

17.4'

123-111

650-6000

29'-4"

16'-0"

20'-1

1

8

"

4

7'-0"

168"

75

17.4'

124-111

1000-7500

29'-4"

20'-0"

20'-1

1

8

"

5

7'-0"

168"

75

17.4'

125-111

1000-7500

33'-4"

20'-0"

20'-1

1

8

"

5

7'-0"

216"

75

17.5'

126-111

1000-9000

33'-4"

24'-0"

20'-1

1

8

"

6

7'-0"

216"

100

17.5'

127-111

1500-10500

33'-4"

28'-0"

20'-1

1

8

"

7

7'-0"

216"

100

17.6'

Advertising