31005009 01 November 2003

Field Wiring Guidelines

Overview

This section contains wiring guidelines and precautions for wiring the
170AMM11030 Momentum I/O base.

Terminal
Connector

To connect field devices to the I/O base, you need a field wiring terminal connector.
Schneider Electric sells terminal connectors in sets of three.

Busbar May Be
Required

Depending on the type of field devices you are using, you may need a 1-, 2-, or 3-
row busbar. The following busbars are available from Schneider Electric.

Mapping
Terminal Blocks
and Busbars

The following table shows the mapping of terminal blocks and optional busbars.

Type

Part Number

Screw-in

170 XTS 001 00

Spring-clip

170 XTS 002 00

Type

Number of Rows

Part Number

Screw-in

1 - row

170 XTS 006 01

2 - row

170 XTS 005 01

3 - row

170 XTS 004 01

Spring-clip

1 - row

170 XTS 007 01

2 - row

170 XTS 008 01

3 - row

170 XTS 003 01

Row #

Terminal #

Connection

Function

2

1-8

01 ... 08

Discrete outputs 1-8

9-10

AI1, AI2

Analog inputs 1-2

11 & 13

AO1+, AO2+

Analog outputs 1-2

12 & 14

AO1-, AO2-

Return for analog outputs 1-2

15

AGND

Return for analog inputs

16

Return for discrete outputs

17

Return for outputs

18

+DC power for outputs

3

1-16

I1 ... I16

Discrete inputs 1-16

17

Return

18

+DC power

4

1-18

PE

Earth ground for field devices, PE analog ground