31005009 01 November 2003

13

Register for Outputs

Overview

170AMM11030 analog and discrete output channels are configured by entering the
appropriate information in output words 1 through 5 as follows.

Note: The module will go to fail state values if network or communication adapter
ATI communication is lost.

Word

Function

1

System information

2 Register for discrete reaction in a fail state

and values

3

Register for analog reaction in a fail state

4

User defined analog fail state values for channel 1

5

User defined analog fail state values for channel 2

6

State of the 8 discrete outputs

7

Analog output word channel 1

8

Analog output word channel 2