Analog Input Register
Each word in this range contains a left justified 15 bit data field. The range is from
0H to 7FFE hex, but the resolution is 14 bit (0 ... 32766 decimal or 0 ... 7FFE hex).

Words 5 ... 8

Words 5 ... 8 are not used.

3x Registers

The 3x registers traffic copped to this module are used for input data as follows.

Range

I/O Map Register

Data Type

3x + 1

Data for discrete input

3x + 2

Data for analog input channel 1

3x + 3

Data for analog input channel 2

Input Voltage

Data is Left

Justified

Comment

Input Range

-10.000 ... +10.000

00382 ... 32382

Nominal input voltage range

Input Over Range

+10.000 ... +10.238 32384 ... 32764

Linear over range input

voltage

Input Out of Range

≥10.238

32766 (7FFE Hex) Input voltage exceeding

threshold may damage the

module.

Input Under Range -10.238 ... -10.000

00002 ... 00382

Linear under voltage range

Input Out of Range

≤-10.238

00000

Input voltage exceeding

threshold may damage the
module.