31005009 01 November 2003

Range

Output Operating Range

Register for Inputs

Overview

The input register is arranged as follows.

Output Voltage

Data is Left Justified Comment

Output Range

-10.000 ... +10.000

00382 ... 32382

Nominal output voltage
range

Output Over Range

+10.000 ... +10.238 32384 ... 32764

Linear over range

output voltage

Output Out of Range

≥10.238

32766

(7FFE Hex)

Threshold limited to

32766 decimal

Output Under Range

-10.238 ... -10.000

00002 ... 00382

Linear under voltage
range

Output Out of Range

≤-10.238

00000

Threshold limited to

00000

Word

Function

1

Status word (module status)

2

State of the 16 discrete inputs

3

Analog input word channel 1

4

Analog input word channel 2

5 ... 8

Not used