Schneider Electric 170AMM11030 User Manual
Page 8
8
31005009 01 November 2003
Discrete Outputs
The following table contains specifications for discrete outputs.
Description
Solid state switch
Operating Voltage
16 - 42 VDC
Absolute Minimum Voltage
12 VDC
Absolute Maximum Voltage
45 VDC
Maximum Voltage
50 VDC for 1 ms
Number of Points
8
Number of Groups
1
Points per Group
8
Current Capacity
250 mA per point 2 amps per module
Type of Signal
True high (sourcing)
Leakage Current
< 1 mA @ 42 VDC
Surge Current
5 amps for 1 ms
On State Voltage Drop
< 1.0 VDC max at 0.25 amp current
Fault Sensing
Overload and short circuit
Fault Reporting
System bit
Response Time
1.8 ms OFF to ON
1.8 ms ON to OFF
CAUTION
Discrete VDC outputs incorporate thermal shutdown and overload
protection.
The output current of a shorted output is limited to a nondestructive
value. The short circuit heats the output driver, and the output will switch
off. The output will switch on again if the driver leaves the over
temperature condition and the user resets the output under program
control. If the short circuit still exists after the output point is reset, the
driver will reach the over temperature condition again and will switch off
again.
Failure to follow this precaution can result in injury or equipment
damage.