3 controller power, 4 battery charging, 3 lcd display – Kohler Power Systems 14/20RESA User Manual

Page 53

Advertising
background image

TP-6804 12/11

53

Section 4 DC2 Controller Operation

4.2.3

LCD Display

The controller is equipped with a two-line x 16 character
backlit digital display with adjustable contrast. When the
generator set is running, the messages shown in
Figure 4-5 are displayed. When the system is in AUTO,
the LCD display steps through the status messages
shown in Figure 4-6.

When a fault or warning condition exists, the controller
will show the corresponding message. See Section 2.5
for more information on fault and warning messages.

The display backlight turns off after about a minute of no
activity. The backlight turns on when a button is pressed
or when the generator set starts.

Running
ATS: Normal *

Voltage: 240V
Freq:

60.0Hz

Engine:

123F

Oil Pressure: OK

Battery

12.3V

Runtime: 12345.6 h

Next Exercise:

7d 6h 42m

Sample data shown.

Active Alert
(if any)

OnCue Status:

Disconnected

[

* Model RXT ATS required
[ OnCue status is displayed only if OnCue password has

been reset.

Figure 4-5

Status Displays, Generator Running

Genset State
Standby

Battery

12.3V

Runtime: 12345.6 h

Next Exercise:

7d 6h 42m

Sample data shown.

Active Alert
(if any)

Next Maint:

123h or 12months

OnCue Status:

Disconnected

[ OnCue status is displayed only if OnCue password has

been reset.

Figure 4-6

Status Displays, Generator in Standby

4.3 Controller Power

The DC2 controller is powered by the generator set
engine starting battery.

Note: To disconnect controller power, disconnect the

utility power to the generator set and disconnect
the battery (negative lead first).

4.4 Battery Charging

The controller includes a built-in battery charger to
maintain the engine starting battery. The DC2 controller
monitors the battery voltage and provides a constant
14

±2% VDC voltage and maximum 2.5 amps to

charge the battery.

The installer must connect 120 VAC/60Hz utility power
provided from the building on a breaker-protected circuit
for the built-in battery charger.

See the Installation

Manual for instructions to connect power.