58

Section 5 Scheduled Maintenance

5.1.1

Service Schedule, 14RESA/RESAL Models

System Component or Procedure

See

Section

Procedure

Frequency

Visually

Inspect

Check

Change

Clean

Test

Fuel

Flexible lines and connections

X

R

Quarterly

Main tank supply level

X

Weekly

Fuel piping

X

Yearly

Lubrication

5.2

Oil level

X

X

8 hours or
before use

Crankcase breather hose

X

Yearly or 500 hours

Change oil

X

Yearly or 100 hours

Replace filter

X

Yearly or 200 hours

Cooling

5.5

Air ducts, louvers

X

X

Yearly

Exhaust Line

5.6

Leakage

X

X

Weekly

Insulation, fire hazards

X

Yearly

Obstructions or combustible materials near exhaust
outlet

X

Weekly

DC Electrical System

5.7

Battery charger operation, charge rate (if equipped)

X

Monthly

Remove corrosion, clean and dry battery and rack

X

X

Yearly

Clean and tighten battery terminals and inspect
boots

X

X

Yearly

Battery electrolyte level and specific gravity *

X

Yearly

AC Electrical System

Tighten control and power wiring connections

X

Yearly

Remote control system, if equipped

X

Monthly

Visible wear or damage

X

Quarterly

Wire abrasions where subject to motion

X

X

Six Months

Wire-cable insulation condition

X

3 Years or 500 hours

Engine and Mounting

Visible wear or damage

X

Weekly

Air cleaner and precleaner service

[

5.4

R

Yearly or 100 hours

Spark plugs

5.3

X

Yearly or 300 hours

Replace stepper motor coupling and bushing

D

500 hours

Generator

Visible wear or damage

X

Quarterly

Exercise generator set

X

Weekly

Brushes and collector ring

D

D

Yearly

Measure and record resistance readings of
windings with insulation tester (Megger

r, with

SCR assembly or rectifier and load leads
disconnected) *

D

3 Years

General Condition of Equipment

Evidence of vibration, leakage, excessive noise,
temperature, or deterioration

X

X

X

Weekly

Interior of sound enclosure

X

X

Quarterly

* Not necessary for maintenance-free batteries.