NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

(*Insert bottom is the metal lip below the lower gold trim bar).

Note: Hearth protection to be min. /8” (10mm) thick non-
combustible or equivalent, with a k factor of .84.

i

nsert

l

eveling

The FireStar™ insert comes with four 3/8”X 3” leveling bolts

(two for use at the rear and two at the front of the insert).

The two at the rear can be used to raise the back of the insert

resting on the fireplace hearth. The two at the front can be

used to adjust the front of the insert on the hearth extension.

To install the bolts a 3/8” nut should be threaded onto the

bolt, followed by a 3/8” flat washer. The bolt should then

be installed from the under side of the insert into the captive

nut in the bottom of the insert. When the bolt is adjusted

to the proper height the nut previously threaded onto the

bolt can be snugged up to the insert bottom.

Hearth / Floor Protection

m

inimum

C

learanCes

to

C

ombustibles

The letters below, C through H, correspond to Figure 4

showing minimum clearances required from the appliance

to combustibles and the minimum projection of the hearth

extension.

C = 6.5” to Side Facing (3/4” or less)

D = 11” to Side Wall

E = 24” to Mantel** (more than 3/4”)

F = 14.5” to Top Facing (maximum thickness 3/4”)

h

earth

p

roteCtion

G = Minimum Hearth Protection from Front of Insert*

H = Vertical Distance from Insert Bottom to Combustible

Material.

C

learanCes

Figure 4

E**

F

H

D

C

Trim

Mantel

G

G

23”

20”

17”

0”

H

0”

2”

4”

6”

**The minimum distance from the top of the insert to a

combustible may be reduced to 16” with a mantel shield.

The shield should be made from 18-gage or thicker sheet

metal, 7” by 33”. The shield must be centered over the

insert and spaced one inch below the mantel. The shield

can be fastened to and spaced from the mantel using four

to six screws.