Table 2 setup functions, default values and ranges, Select options, Table 3 unit options – Liebert CHALLENGER 3000 User Manual

Page 16: Calibrate sensors, Show dip switches, Table 4 dip switch settings, Table 2, Setup functions, default values and ranges, Table 3, Unit options

Advertising
background image

Operation with Advanced Microprocessor Controls

8

Table 2 lists the setup functions, their factory default values and the allowable programming ranges.

Select Options

The following table lists options which should match the options installed with your unit and should

not need to be changed during normal operation.

Calibrate Sensors

The temperature and humidity sensors can be calibrated by selecting this menu item. “SENSOR”

shows the actual sensor reading or raw reading. “CALIBRATED” shows the sensor reading after the

calibration offset has been added. The temperature sensor can be calibrated ±5 degrees Fahrenheit

and the humidity sensor can be calibrated ±10%RH. When calibrating the humidity sensor, the value

shown will always be % RH, even though absolute humidity control may be selected. If absolute

humidity control is selected, the Normal Status Display will display the adjusted reading and may not

agree with the relative humidity reading displayed while in calibration.

Show DIP Switches

The DIP switch settings can be reviewed from the display panel. Changing the DIP switches requires

opening the upper panel for access to the DIP switches on the microprocessor control board.

The selections shown in Table 4 should match options installed on your unit and should not need to

change during normal operation. Switches 1 through 7 are self explanatory. DIP switch 8, not shown in the

table, enables the password feature when set to ON and disables the password feature when set to OFF.

Table 2

Setup functions, default values and ranges

Function

Default

Range

Cold Start Time Delay*

3

0 to 3 min (0 = no delay)

Restart Time Delay

0.1

0 to 9.9 min (0 = manual restart)

Infrared Fill Rate

150

110 to 500%

Chilled/Hot Water Coil Flush

24

0 to 99 hrs (also Econ-O-Coil)

C/F Degrees

F

C or F

*Factory set to 0 for water cooled, glycol, and GLYCOOL units.

Table 3

Unit options

Option

Selection

Heating

1

Yes or No

Humidifier

Yes or No

Dehumidifier

Yes or No

Hot Gas Reheat

2

Yes or No

Heat Stages

3

2

1

Heating cannot be disabled on units with SCR reheats.

2

Hot gas reheat not available on units with SCR reheats.

3

Heat stages not selectable on units with SCR reheats.

NOTE
Power MUST be cycled OFF, then ON from the unit disconnect switch for the control

system to update the DIP switch settings (with the exception of switch 8).

Table 4

DIP switch settings

Switch #

Off

On

1

No Part Coil

Part Coil/Chilled Water

2

Electric/Hot Gas Reheat

Hot Water Reheat

3

All

Not Used

4

No GLYCOOL

GLYCOOL

5

No Dual Cooling

Dual Cooling

6

Not Used

Not Used

7

a

Tight Control

Standard Control

a

SCR reheats only (with special software); otherwise, not used.