Component Operation and Maintenance

45

6.3

Blower Package

Periodic checks of the blower package include: belt, motor mounts, fan bearings, and impellers.

6.3.1 Fan Impellers and Bearings

Fan impellers should be periodically inspected and any debris removed. Check to see if they are

tightly mounted on the fan shaft. Rotate the impellers and make sure they do not rub against the fan

housing.
Bearings used on the units are permanently sealed and self-lubricating. They should be inspected for

signs of wear when the belt is adjusted. Shake the pulley and look for movement in the fan shaft. If

any excessive movement is noticed, bearings should be replaced. However, the cause of the wear must

be determined and corrected before returning the unit to operation.

6.3.2 Belt

The drive belt should be checked monthly for signs of wear and proper tension. Pressing in on belts

midway between the sheave and pulley should produce from 1/2" to 1" (12 to 25 mm) of movement.

Belts that are too tight can cause excessive bearing wear.
Belt tension can be adjusted by raising or lowering the fan motor base. Loosen nut above motor

mounting plate to remove belt. Turn nut below motor mounting plate to adjust belt tension. If belt

appears cracked or worn, it should be replaced with a matched belt (identically sized). With proper

care, a belt should last several years.

6.3.3 Air Distribution

All unit models are designed for constant volume air delivery. Therefore any unusual restrictions

within the air circuit must be avoided. Refer to the following table for recommended free area for

proper air flow.

Grilles used in raised floors vary in size, the largest being 18" x 6" (46 cm x 15 cm). This type of grille

has approximately 56 in

2

(361 cm

2

) of free area. Perforated Panels are usually 2' x 2' (61 cm x 61 cm)

and have a nominal free area of approximately 108 to 144 in

2

(697 to 929 cm

2

).

NOTE
After adjusting or changing the belt, always be certain that motor base nuts are tightened.

The bottom adjustment nut should be finger tight. The top locking nut should be tightened

with a wrench.

Table 17

Recommended free area ft

2

(m

2

) for grilles or perforated panels at output velocities of

550 and 600 fpm (2.8 and 3.1 m/s)

Model

550 FPM

(2.8 m/s)

600 FPM

(3.1 m/s)

60 Hz Units

3 Ton

2.5 (0.22)

2.3 (0.21)

5 Ton

3.8 (0.34)

3.5 (0.33)

50 Hz Units

3 Ton

2.9 (0.27)

2.6 (0.24)

5 Ton

3.5 (0.33)

3.3 (0.31)

NOTE
Absolutely avoid any under-floor restrictions such as clusters of cables or piping. Whenever

possible, cables and pipes should be run parallel to the air flow. Never stack cables or piping.