4 heating operation, Electric reheat, Hot water reheat – Liebert CHALLENGER 3000 User Manual

Page 39: 2 humidity control, 2 response to control types, Proportional control, Pid control (chilled water or scr reheats only), Intelligent control (chilled water only), 3 dehumidification operation, Heating operation

Advertising
background image

System Performance with Advanced Microprocessor Controls

31

4.1.4 Heating Operation

Electric Reheat

The two heat stages are activated when the temperature control calculates a requirement of 50% and

100%, respectively. Each stage is deactivated when the heat requirement is 25% less than the activa-

tion point.

Hot Water Reheat

The solenoid valve opens when the requirement for heating is 100% and closes when the requirement

drops below 50%.

SCR Electric Reheat (Requires Special Control Software)

The SCR (Silicon Controlled Rectifier) controller shall proportionally control the stainless steel

reheats to maintain the selected room temperature. The rapid cycling made possible by the SCR con-

troller provides precise temperature control, and the more constant element temperature improves

heater life. During operation of the SCR control, the compressor operates continuously. The heaters

are modulated to provide temperature control.
On units equipped with SCR Reheats, unit operation can be controlled even further with DIP switch

#7 on the control board. With DIP switch #7 in the “OFF” position, or “Tight Control,” the compressor

is locked on and the SCR Reheats are modulated for very tight temperature control. In the event of a

malfunction of the SCR Reheats, the compressor will be turned off if the temperature drops to the

Low Temperature Alarm Setpoint. With DIP switch #7 in the “ON” position or “Standard Control,”

the compressor will cycle on and off as required to satisfy the requirements for cooling and dehumidi-

fication in a similar manner as a standard unit without SCR Reheats, i.e., Temperature Setpoint

PLUS Temperature Sensitivity PLUS 1°F. The SCR Reheats are modulated from 0% to 100% as

required to satisfy the requirements for heating over a control band from the Temperature Setpoint

MINUS the Temperature Sensitivity MINUS 1°F.

4.2

Humidity Control

4.2.1 Dehumidification/Humidification Required, in Percent

The humidity control program for the Advanced Microprocessor is based on a calculated % require-

ment for dehumidification/ humidification.

4.2.2 Response to Control Types

Proportional Control

The % requirement is determined only by the difference between the return air humidity and the

humidity setpoint. As the return air humidity rises above the humidity setpoint, the % dehumidifica-

tion required increases proportionally from 0 to 100% over a humidity band equal to the humidity

sensitivity setting. The converse is true for % humidification requirement.

PID Control (Chilled Water or SCR Reheats only)

If PID control is selected, humidity is controlled in the proportional mode with the sensitivity band

being determined by the humidity sensitivity setpoint.

Intelligent Control (Chilled Water only)

If intelligent control is selected, the return air humidity is controlled at or near the humidity setpoint.

The % dehumidification/humidification required is calculated based on a set of logical “rules” that

simulate the actions of an expert human operator (see 4.3.3 - Intelligent Control (Chilled Water

only)).

4.2.3 Dehumidification Operation

1-Stage Dehumidification, Compressorized Direct Expansion (DX) Systems

Dehumidification with the standard configuration is accomplished by operating the compressor with-

out hot gas bypass active. If system has part coil, dehumidification is accomplished by using only part

coil. If the installation has a very light sensible load, dehumidification will be inhibited at the point at

which 125% heating would be required to prevent overcooling. Dehumidification would be enabled

when the temperature increases to the point where only 50% heating is required.

Advertising