The preset wfs does not match the actual wfs, Troubleshooting and repair, Caution – Lincoln Electric SVM143-A User Manual

Page 57

Advertising
background image

F-13

TROUBLESHOOTING AND REPAIR

F-13

DH-10

Observe all Safety Guidelines detailed throughout this manual.

PROBLEMS
(SYMPTOMS)

POSSIBLE AREAS OF
MISADJUSTMENT(S)

RECOMMENDED
COURSE OF ACTION

The preset arc voltage does not
match the actual voltage.

The preset WFS does not match
the actual WFS.

1. Make sure the power source is

set for remote voltage control.

2. Make sure the DIP switches on

the DH-10 control board are set
correctly for the power source
being used.

1. Check the wiring and connec-

tions between the tachometer
and the control board. See the
Wiring Diagram.

2. Make sure the DIP switches on

the DH-10 control board are set
correctly.

3. The control board may be faulty.

1. The control board may be

faulty.

2. The control cable between the

power source and the DH-10
may be defective.

1. Perform the

Tach Adjustment

and Feedback Test.

FUNCTION PROBLEMS (Continued)

CAUTION

If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact the Lincoln Electric
Service Department for technical troubleshooting assistance before you proceed. Call 216-383-2531 or 1-800-833-9353.

-----------------------------------------------------------------------------------------------------------------------------