Figure 17

13” x 13”

10’ Max.

10’ Max.

Rain Cap

Flashing

Collar

Flashing

Roof Support

Attic

Radiation

Shield

Non-Combustible

Flameproof

Facing

56” Min.

68” Min.

Figure 18

The duct system must be installed respecting the following:

1. Remove the plates closing up the 8” dia. holes on top of the fireplace.

Then, cut the insulation in order to obtain two 8” dia. openings. Fix

the adaptors on the fireplace openings by turning clockwise (Figure

16).

2. Maintain at least a 2” (50 mm) clearance between the ducts and any

combustible material; the required hole size is 13” x 13” (330 mm x

330 mm).

Exception #1: For the grills, the framing can be 10-3/4” x 10-

3/4” (275 mm x 275 mm) to provide the clearance as required

by the integral spacers on the double outlet duct system.

3. The maximum number of elbows in a run of duct is two.

4. Maintain at least 6-1/2” (160 mm) clearance from the outlet grill

framing to a combustible ceiling, side wall or mantel.

5. When traversing a combustible wall or floor, a firestop must be installed

at the wall or floor penetration. The hole size must be 13” x 13” (330

mm x 330 mm)

6. Do not connect the hot air ducts to a central heating system. Malfunc-

tion of the heating system’s blower will cause the fireplace to overheat.

A furnace duct is only single wall and not double wall as is required
for the Montecito Estate™ hot air exhaust.

7. Use only Security Chimneys International grills and components as

described in this manual. Other grills or registers may be too restric-

tive and may overheat the fireplace or ceiling.

8. Do not use insulated flexible ducts as they will overheat.

9. Do not use tees or any other components than the ones specifically

listed here.

10. Never allow the ducting to pitch down as hot air will be trapped creat-

ing a fire hazard. Never route the ducting downwards.

11. The hot air outlet grills must be installed with the louvers pointing

downwards in order to prevent overheating adjacent ceilings.

Figure 16

When installing the double outlet system, the hot air outlets can be

installed in the same room as the fireplace, or one or both of the outlets

can be installed in adjacent or upper rooms. Installing the ducts at dif-

ferent elevations will tend to exhaust more heat out of the higher outlet

(Figure 17).

Frame

Grill

Maintain at least 6-1/2”

(160 mm) clearance from

the outlet grill framing to

a combustible ceiling,

side wall or mantel.

Outlet Grill

Outlet Grill

WARNING: The outlet

grills should not be

installed facing up-

ward through a floor.

Danger of burns can

result if grills in floor

are stepped on.

6-1/2” Min.

(to ceiling)

Firestop

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.