CHIMNEY INSTALLATION INSTRUC-

TIONS

1. Cut and frame the holes in the ceiling, floor

and roof where the chimney will pass (see

Figure 22). Use a plumb bob to line up the

center of the holes. The sizes are indicated

in Table 2 for the floor and ceiling holes

and Table 3 (Page 15) for the roof holes.

From below, install a firestop in each ceiling/floor

separation through which the chimney will pass.

At the attic level, install an attic radiation shield

from above (Figures 23a & 23b).

2. For Secure Temp

S2100+ / Nova Temp

HT6000+ / Secure Temp

GX chimneys, place

the first chimney length on the fireplace.

To lock it in place, turn 1/4 of a turn clock-

wise. With the ACBI chimney, you must

use a starter section before installing the

first chimney length (Figure 24). Continue

installing chimney lengths making sure to

lock each length in place.

3. Every time the chimney passes through a ceil-

ing or a wall, install the appropriate firestop.

When you reach the desired height, install the

roof support (Refer to instructions included

with the support). For an ACBI chimney use

an universal support AC10SU.

4. Put the roof flashing in place and seal the

joint between the roof and the flashing

with roofing pitch (see Figures 25 & 26).

For sloping roofs, place the flashing under

the upper shingles and on top of the lower

shingles. Nail the flashing to the roof, using

roofing nails.

5. Place the storm collar over the flashing, and

tighten it with the bolt supplied. Finally, seal

the joint between the storm collar and the

chimney, using silicone caulking.

6. Install the chimney cap.

CHIMNEY MODEL

SqUARE HOLE

SIZE OPENING

Secure Temp™

S2100+

Nova Temp™

HT6000+

Secure Temp

GX

15 in (380 mm)

ACBI: Ceiling

(1” clearance)

Wall

15 in (380 mm)

17 in (432 mm)

Note: See Table 3 for Sloped Roof Framing

Table 2 - Flat Roof Framing

Figure 22 - Roof Framing

Figure 23a

S2100 / HT6000+

Solid Packed Pipe

ACBI

Air Cooled Pipe

Figure 23b

Figure 24

CHIMNEY INSTALLATION

MODEL ACBI

Rain Cap

Collar

Flashing

Attic Radiation

Shield

Firestop

Universal Support

ACBI Starter Section

ACBI7SB

or

ACBI7SB30

Note: Outside air kits must be

installed for both fireplace and

ACBI chimney.

Outside Combustion

Air Kit

Optional Chimney

Outside Air Intake

Attic Radiation Shield

Attic Radiation

Shield

Radiation Shield

Firestop

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.