OUTSIDE AIR KIT

It is mandatory to install an outside air connection to the Montecito
Estate™. The following components are required and are included with

the fireplace:

- Outside air kit (includes 40 inch flex that goes up to ten (10) feet

long)

- 4” Adaptor for fireplace connection

Outside Air Installation

The outside air assembly may be installed according to the following

requirements:

A) Duct length should be kept to a minimum. The maximum length of a

4” interior diameter (100 mm) insulated flexible duct is 20 feet (6.1 m).

The duct can be extended to a maximum of 40 feet (12 m) using a 6”

interior diameter (150 mm) insulated flexible duct (See note below).

B) The air intake register must not be installed more than ten (10) feet

(3050 mm) above the base of the fireplace.

C) The fresh air must come from outside the house. The air intake must

not draw air from the attic, basement or garage.

D) The air intake should be installed where it is not likely to be blocked by

snow or exposed to extreme wind and away from automobile exhaust

fumes, gas meters and other vents.

E) The duct and register may be installed above or below floor level.

Make a 4-1/4” (110 mm) hole in the outside wall of the house at the chosen

location. From outside, place the outside air register in the hole (open

side down) and fasten the register to the wall with screws as shown (see

Figure 19). Slip the pipe into the insulated sleeve. Place the insulated

pipe over the register tube and over the fireplace’s outside air connector

(see Figure 20). At each end, carefully pull back the insulation and plastic

cover exposing the flexible pipe. Using the aluminium tape provided,

wrap the tape around the joint between the flexible pipe and the air inlets.

Carefully push the insulation and plastic cover back over the pipe. Using

aluminium tape, fasten the plastic cover in place.

NOTE: We recommend not to exceed 20 feet of 4” flexible pipe. If you

require a longer length we recommend that you use a 5” diameter flex-

ible pipe for the complete run up to 30 feet and a 6” diameter pipe for a

run of up to 40 feet.

Figure 19

OUTSIDE CONNECTION

Outside

Intake

Screw

Opening

Facing

Down

Wall

Aluminum Tape

Plastic

Cover

Insulation

Flexible Pipe

Aluminum Tape

Figure 20

Aluminum Tape

Aluminum Tape

Fireplace

Connection

Plastic

Cover

Insulation

Flexible Pipe

Fireplace

OUTSIDE AIR CONNECTION TO THE FIREPLACE

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

12