ANGLED WALL RADIATION SHIELD

(XRSMI30 and AC10RSMI30)

When traversing a combustible wall with the chimney at a 30º or 45º

angle, an angled firestop or wall radiation shield must be installed. Only

one is required.

Note: 45º angle for Canada only (XRSMI45).

In cold climate locations (climates where temperatures will fall below 32º

F / 0º C), we recommend that you use the insulated wall radiation shield

since it will maintain the home’s thermal barrier.

XRSMI30 and AC10RSMI30

(XRSMI45 - Canada Only)

Chimney Model (7” dia).

Angle

Hole Size

Secure Temp™

S2100+

Nova Temp™

HT6000+

Secure Temp

GX

(US only)

30º

15” x 38-1/4”

(380 mm x 972 mm)

Secure Temp

S2100+

Nova Temp

HT6000+

45º

Canada only

15” x 25-7/8”

(380 mm x 657 mm)

ACBI

30º

17 x 42-1/2”

(432 mm x 1080 mm)

Table 5

Figure 30

Drywall

Insulated Wall

Insulated Wall

Radiation Shield

CHIMNEY SUPPORT INSTALLATION

Universal Roof Support

This support has three possible uses:

1. For Secure Temp S2100+ / Nova Temp

HT6000+ / Secure Temp

GX, it

must be used on a roof to support the chimney.

2. It may be used on a floor, ceiling or roof above an offset to support

the chimney above the offset.

3. It may be used on a floor, ceiling or roof as a supplementary support

when the chimney height exceeds 15 feet (4.6 m).

Table 6 gives maximum height of supported chimney.

NOTE: For the ACBI chimney, a support section (ACBI7SL) must be used

every 30 feet (9m) or an universal support every 20 feet (6m) instead of

the universal roof support (ST).

CHIMNEY

MAXIMUM HEIGHT OF

SUPPORTED CHIMNEY

7” Diameter

Offset Support

Roof Support

Secure Temp

S2100+

Nova Temp

HT6000+

Secure Temp

GX

16 feet (5.49 m).

18 feet (6.1 m).

ACBI

40 feet (12.19 m).

50 feet (15.20 m).

Table 6

CHIMNEY CHASE AND MULTIPLE TERMINATIONS

For the purpose of this manual, a chimney chase is considered a part of

the chimney system rather than part of a building. The termination must

be placed a minimum of 18” (460 mm) above the chase.

For installations where more than one chimney is located in the same

chase or within the same area, we suggest that their terminations be

separated by at least 16” (410 mm) horizontally, and 18” (460 mm) verti-

cally. This separation is to prevent smoke migrating from one chimney

to another (see Figure 31).

Figure 31

18” (460 mm)

16” (410 mm)

18” (460 mm)

18” (460 mm)

16” (410 mm)

For roof support installation, refer to the instructions provided with the

support.

Universal Offset Support

This support is used to support the chimney above an offset. When

the chimney offset is used to traverse a wall this support may be used

on the wall to support the chimney. The maximum heights are given in

Table 6. For offset support installation, refer to the instructions provided

with the support.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.