Default thermostat settings, Thermostat output table – Lennox International Inc. 51M37 User Manual

Page 44

Advertising
background image

Page 8

505069M 07/05

Default Thermostat Settings

Default thermostat settings are shown in table 2 and the
default program is shown in table 3.

Table 2

Default Thermostat Settings

Mode

Heat (Perm. Hold)

Heat Setpoint (Perm Hold)

70°F (or 21°C)

Cool Setpoint (Perm Hold)

78°F (or 26°C)

Fan

Auto

Filter Reminder

OFF

Maintenance Reminder

OFF

Equipment Protection Timers

Reset Back to Zero

Autochangeover

OFF

Table 3

Default Program Settings − Time & Temp.

Programs

Time

Temp. − Heat

Temp. − Cool

All days − A

6:00am

70

_F / 21°C

78

_F / 26°C

All days − B

8:00am

62

_F / 17°C

85

_F / 29°C

All days − C

6:00pm

70

_F / 21°C

78

_F / 26°C

All days − D

10:00pm 62

_F / 17°C

82

_F / 28°C

Thermostat Output Table

Table 4 depicts the 51M42 thermostat output states for var-
ious input conditions. The following notes described terms
used in the table.

NOTES:

S X = output is activated with 24VAC.
S BBP: outdoor temperature is below balance point
S ABP: outdoor temperature is above balance point
S In all cases, the state of the B terminal is opposite that

of the O terminal

S Data are tabulated for AUTO fan setting. If the fan set-

ting is ON, the G output is activated in all cases

S Upstage timers:

30 minutes (when upstaging from small to large
demand)

15 minutes (HEAT MODE ONLY − when upstaging
from large to very large demand)

S The temperature ranges expressed in the following

definitions of SMALL/LARGE/VERY LARGE" de-
mands are for guidance only; actual temperatures
may vary:

With a SMALL heat demand, temperature is:
below setpoint –0.5F but above setpoint –1.5F
AND 30-minute upstage timer HAS NOT expired.

With a LARGE heat demand, temperature is:
less than setpoint –1.5F
OR 30-minute upstage timer HAS expired.

With a VERY LARGE heat demand, temperature is:
below setpoint –2.5F
OR 15−minute 2

nd

upstage timer HAS expired.

Emergency heat demand (only if emergency heat is
enabled): temperature is below setpoint –0.5F.

With a SMALL cool demand, temperature is:
above setpoint +0.5F but below setpoint +1.5F
AND 30-minute upstage timer HAS NOT expired.

With a LARGE cool demand, temperature is:
above setpoint +1.5F
OR 30-minute upstage timer HAS expired.

Table 4

THERMOSTAT OUTPUTS

Demand Condition

W1

E

Y1

Y2

G

O

Cooling Demands

SMALL

X

X

X

LARGE

X

X

X

X

No Demand

X

Heating Demands

With Electric Backup

(no outdoor sensor)

SMALL

X

X

LARGE

X

X

X

VERY LARGE

X

X

X

X

Emergency

X

X

No Demand

With Gas Backup

(dual fuel; no outdoor sensor)

SMALL

X

X

LARGE

X

X

X

VERY LARGE

X

Emergency

X

No Demand

With Electric Backup

(outdoor sensor attached)

SMALL (Above Balance Point)

X

X

LARGE (ABP)

X

X

X

VERY LARGE (ABP)

X

X

X

SMALL (Below Balance Point)

X

X

LARGE (BBP)

X

X

X

VERY LARGE (BBP)

X

X

X

X

Emergency

X

X

No Demand

With Gas Backup

(dual fuel; outdoor sensor attached)

SMALL (ABP)

X

X

LARGE (ABP)

X

X

X

VERY LARGE (ABP)

X

SMALL (BBP)

X

LARGE (BBP)

X

VERY LARGE (BBP)

X

Emergency

X

No Demand