Important – Lennox International Inc. 51M37 User Manual

Page 9

Advertising
background image

Page 9

51M37 SERIES 5/2

Smart Setback Recovery (via DIP switch #6)

Smart Setback Recovery (SSR) affects the way the ther-
mostat responds to program events. If SSR is disabled, the
thermostat will react to a program event at the time the
event occurs. However, if SSR is enabled, the thermostat
will react to a program event before the event occurs such
that the desired temperature is reached at the time of the
event, not after.

Fan Control

AUTO or ON modes.

I/O Relays

All thermostat relays are latching type to minimize power
consumption.

Table 4

51M37 Terminal Designations

Term. Description

B

Reversing valve, heat active

O

Reversing valve, cool active

R

24VAC

Y1

First-stage cooling/heating, compressor
energized

W1*

Auxiliary heating, furnace energized

Y2

Second-stage cooling/heating, compressor
energized

E*

Emergency heat

G

Fan control

L

Service Indicator

C

24VAC common

T

Outdoor temperature sensor connection 1

T

Outdoor temperature sensor connection 2

* For most applications, E will be jumpered to W1. If sep-
arate wires are not provided for both E and W1, jumper
the E terminal to the W1 terminal on the thermostat sub-
base. For applications involving the use of a balance
point (whereby the outdoor temperature is to be used to
restrict either heat pump operation or backup heat
source operation), the optional outdoor sensor (part
number X2658) MUST be installed.

Equipment Protection Timers

Minimum Compressor OFF time: 5 minutes
Minimum Compressor ON time: 4 minutes
Minimum Furnace ON time: 3 minutes

Minimum furnace cycle time (elapsed time between any
furnace activation and the next furnace activation): 6 min-
utes.

Minimum elapsed time between any compressor activa-
tion and the next compressor activation: 6 minutes.

NOTE − All protection timers (except the compressor OFF
timer) can be over−ridden if a heating or cooling demand is
initiated or terminated using the UP, DOWN, HEAT, or
COOL buttons.

Equipment Protection Override

Both the minimum compressor OFF timer and the mini-
mum equipment cycle timer can be over−ridden by press-
ing and holding either the HEAT or COOL button down for 4
seconds.

Over−Temperature Protection

Thermal-mechanical switch opens W1, Y1, Y2, and E at
93°F+/−6°F.

Filter Reminder

Settings of Off, 1, 3, 6 or 12 (months of fan run time) are
available. When programmed time has elapsed, a FILTER
indicator is displayed.

Maintenance Reminder

Settings of Off, 6 or 12 (months of chronological time) are
available. When programmed time has elapsed, a mainte-
nance indicator MAINT" is displayed.

Service Reminder

The SERVICE indicator is displayed only under the follow-
ing conditions:

S

if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is
shorted to the R terminal;

OR

S

if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is
shorted to the C terminal.

Power Loss/Recovery

Thermostat memory is retained for a minimum of 24 hours
during a power loss (includes retention of program infor-
mation, HOLD status, programmed temperature setpoint,
heat/cool and fan mode settings, filter reminder status,
maintenance reminder status, and equipment protection
timers). After 24 hours of power loss, programmed settings
will be lost and replaced with default settings.

IMPORTANT

Power must be applied for at least six consecutive
hours prior to a power loss in order for memory to
be retained for the specified time.

LCD Backlight

Activated for 30 seconds when any button is pressed.

NOTE − During an electrical storm or similar disturbance,
the backlight may activate for a few seconds. This is nor-
mal and will no longer occur after the electrical disturbance
has passed.

Thermostat Operating Conditions

35°F to 105°F, 5% to 90% RH

Thermostat Storage Conditions

−40°F to 185°F, 5% to 95% RH

Advertising