505050M 5/1/05

Default Thermostat Settings

Default thermostat settings are shown in table 2 and the
default program is shown in table 3.

Table 2

Default Thermostat Settings

Mode

Heat (Permanent Hold
Mode)

Setpoint

70°F (or 21°C)

Fan

Auto

Filter Reminder

OFF

Maintenance Reminder

OFF

Equipment Protection
Timers

Reset Back to Zero

Table 3

Default Program Settings

Programs

Time

Temperature
(Heat)

Temperature
(Cool)

Weekday − A

6:00am

70

_F / 21°C

78

_F / 26°C

Weekday − B

8:00am

62

_F / 17°C

85

_F / 29°C

Weekday − C 6:00pm

70

_F / 21°C

78

_F / 26°C

Weekday − D 10:00pm 62

_F / 17°C

82

_F / 28°C

Weekend − A 6:00am

70

_F / 21°C

78

_F / 26°C

Weekend − B 8:00am

62

_F / 17°C

85

_F / 29°C

Weekend − C 6:00pm

70

_F / 21°C

78

_F / 26°C

Weekend − D 10:00pm 62

_F / 17°C

82

_F / 28°C

Weekday

Monday, Tuesday, Wednesday,
Thursday, Friday

Weekend

Saturday, Sunday

Technical Specifications

Thermostat Type

Electronic programmable thermostat for heat pump,
3-stage heat/2-stage cool.

NOTE − 2 stages of heat pump heat and one stage of auxil-
iary (gas or electric) backup heat are supported.

Power Supply Range

18VAC − 30VAC (24VAC nominal), 60Hz

CAUTION

24VAC is present on the terminals of the thermostat
bracket. If removing the thermostat from the wall,
use caution and avoid touching any of the connec-
tor terminals on the wall bracket.

Also, when working with the thermostat dip
switches, use a non−conductive tool and take cau-
tion to avoid making any contact with the circuit
board, its imprinted circuitry and its connector
prongs.

Temperature Display

Display Scale: Fahrenheit or Celsius user selectable (via
DIP switch; see figure 22)
Display range: 35°F (2°C) to 99°F (37°C)
Display resolution: 1°F (1°C)
Display Accuracy: +/−1°F

If the Fahrenheit/Celsius display must be changed, use a
plastic, non−conductive tool to push the dip switch to the
right position (see figure 22).

F/C (Fahrenheit/Celsius) switch
shown in Celsius position

Figure 22

Changing Fahrenheit/Celsius Setting

1
2
3
4
5
6

PLUG IN (Use Care To Avoid Bending Prongs.)

Temperature Measurement Range

Measurement Scale: Fahrenheit
Measurement Range: 35°F to 99°F
Measurement Resolution: 0.5°F
Measurement Accuracy: +/−1°F
Field Offset: via DIP switches to +/−3°F
Sampling Method: temperature measurements sampled
every 15 seconds. Displayed temperature is the average
of the last four measurements.

Temperature Setpoint Range

Setting range: 50°F (10°C) to 90°F (32°C)
Setting resolution: 1°F (1°C)