4092A Operations and Maintenance Manual

13

Table 2

shows an example Telnet session of command sent to the 4092A and the response from the

4092A.

Table 2: Example Telnet session

Command sent

4092A response

S

Status command

S00000,00000

4092A set to A and autoswitch, no active alarms

B

Make channel B active
command

ALARM22000

Alarm output shows change in active input; 4092A set to B with active input set to B.

S

Status command

S22000,22000

4092A set to B with active input set to B. Current status should match last alarm
output (ALARM22000). No latched alarms. Changed status (remote control bit
changed from autoswitch to B and active input changed from A to B).

S

Status command

S22000,00000

4092A set to B with active input set to B. Current status should match last alarm
output (ALARM22000). No latched alarms. Changed status bits cleared upon status
request.

C

Autoswitch command

ALARM02000

Alarm output shows change in status. 4092A set to autoswitch with active input set
to B.

S

Status command

S02000,20000

4092A set to autoswitch with active input set to B. Current status should match last
alarm output (ALARM02000). Changed status (remote control bit changed from B to
autoswitch).

S

Status command

S02000,00000

4092A set to autoswitch with active input set to B. No latched alarms. Changed
status bit cleared upon status request.

None sent; input A lost
signal

ALARM02800

Alarm output shows change in status. 4092A set to autoswitch with active input set
to B. Input A has a fault.

S

Status command

S02800,00800

4092A set to B with active input set to B. Current status should match last alarm
output (ALARM02800). Input A has a latched fault (latched fault will not clear until
input A failure is corrected and subsequent status command is sent).

S

Status command

S02800,00800

Input A still has fault.

S

Status command

S02800,00800

Input A still has fault.

None sent; input A
fixed and has valid
signal

ALARM02000

Alarm output shows change in status. Input A current status changed to OK.

S

Status command

S02000,00800

4092A set to autoswitch with active input set to B. Current status should match last
alarm output (ALARM02000). Input A OK in current status. Input A has a latched
fault.