Do not tilt the cabinet more than, 10˚ during installation – Powerware 9315 User Manual

Page 22

Advertising
background image

16

Powerware 9315 Parallel Redundant System I & O

164202013, Rev. D 041599

Refer to the following while installing the parallel cabinet:

·

Dimensions in this manual are in millimeters and inches.

·

Do not tilt the cabinet more than

10˚ during installation.

·

The conduit landing plates are to be removed to add conduit landing holes as

required. Plate material is 16 gauge steel (0.06 in. thick).

·

Terminals E9–E12 and E16---E18 are UL and CSA rated at 90˚C. A hex key tool

is required to attach wires to the terminals.

·

Details about control wiring are provided in Table A---1 of Appendix A and the

Control Wiring Interconnect Details in Chapter 3 of this manual.

Figure 6 shows typical control wiring and power wiring terminations of the UPS

module and parallel cabinet. Refer to the Powerware 9315 Installation manual

provided with the UPS system for location of UPS module cabinet wiring

terminations.
NOTE: Material and labor for external wiring are to be provided by designated

personnel.

LEFT DOOR

Output

Neutral

Connection

(E12)

TB1

TB2

MOB#2

TB1

Ground

MOB1

E10

E9

MOB#1 TB1

E11

E9

MOB2

E16 E17 E18

E12

E10

E11

ÆA ÆC

ÆB

ÆA ÆC

ÆB

A/C Output

E9, E10,

E11

UPS MODULE

PARALLEL CABINET

Communication Panel

Terminal Strip

TB3

(100--160kVA UPS Shown)

Isolated

Ground

(Optional)

Figure 6. Typical Control and Power Wiring Terminations of UPS Module

and Parallel Cabinet