Powerware 9315 User Manual

Page 53

Advertising
background image

A---9

Powerware 9315 Parallel Redundant System I & O

164202013 Rev. D 041599

5.

External overcurrent protection is not provided by this product, but is required by

codes. Refer to Tables A---3 and A---4 for power wiring recommendations and

requirements for the parallel cabinet. Refer to the

PowerwareÒ 9315 Installation

manual provided with the UPS system for UPS module power wiring requirements.

If an output lockable disconnect is required, it is to be supplied by designated

personnel.

6.

Nonlinear loads can create neutral currents that are greater than 100%. This

product can accommodate double-size neutral terminations if needed. The neutral

bus (E12) in the parallel cabinet has pressure termination size six (6) times that as

listed for the output (E16---E18).

7.

Terminals E9 through E12 and E16 through E18 are UL and CSA rated at 90_C.

A hex key tool is required to attach wires to terminals. Refer to Table A---3 for

power cable terminations. Figure 13 shows the location of the power cable

terminations inside the UPS and parallel tie cabinets.

8.

The ground pressure termination size for all models is: (4) #6---350 kcmil. Tighten

with 3/8 in. internal hex tool to 375 lb-in.

Advertising