Powerware 9315 User Manual

Page 51

Advertising
background image

A---7

Powerware 9315 Parallel Redundant System I & O

164202013 Rev. D 041599

Table A--3. Tie Cabinet Power Inputs and Termination Requirements (cont.)

Internal

Hex Size

(In.)

Tightening

Torque

(lb-in)

Size of

Pressure

Termination

(CU wire)

Function

Terminal

Point in

Tie

Cabinet

Breakers

MOB 1

and 2

(Amps)

Minimum

Conductor

Size

UPS

Output

NP

Voltage

UPS

Model

150

600

3/0 AWG

200

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8-#4, (150)

#3-#1, (200)

#1/0-350

kcmil, (250)

5/16

150

480

4/0 AWG

225

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8-#4, (150)

#3-#1, (200)

#1/0-350

kcmil, (250)

5/16

150

400

350 kcmil 300

E9, E10,

E11

Phase A,

B, C

(2) #2/0-400

kcmil or

(1) #6-600

kcmil

#2-600 kcmil,

(375)

#8-#3, (275)

3/8

150

208

(2) 350

kcmil

600

E9, E10,

E11

Phase A,

B, C

(2) #2/0-400

kcmil or

(1) #6-600

kcmil

#2-600 kcmil,

(375)

#8-#3, (275)

3/8

160

600

3/0 AWG

200

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8-#4, (150)

#3-#1, (200)

#1/0-350

kcmil, (250)

5/16

160

480

250 kcmil 250

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8-#4, (150)

#3-#1, (200)

#1/0-350

kcmil, (250)

5/16

160

400

350 kcmil 300

E9, E10,

E11

Phase A,

B, C

(2) #2/0-400

kcmil or

(1) #6-600

kcmil

#2-600 kcmil,

(375)

#8-#3, (275)

3/8

160

208

(2) 350

kcmil

600

E9, E10,

E11

Phase A,

B, C

(2) #2/0-400

kcmil or

(1) #6-600

kcmil

#2-600 kcmil,

(375)

#8-#3, (275)

3/8

225

208

(2) 300

kcmil

800

E9, E10,

E11

Phase A,

B, C

(3) #3/0-500

kcmil

#3/0-500 kcmil

(375)

3/8

225

480

(2) #4/0

350

E9, E10,

E11

Phase A,

B, C

(2) #2/0-400

kcmil or

(1) #6-600

kcmil

#2-600 kcmil,

(375)

#8-#3, (275)

3/8

300

480

(2) 250

kcmil

450

E9, E10,

E11

Phase A,

B, C

(2) #2/0-400

kcmil or

(1) #6-600

kcmil

#2-600 kcmil,

(375)

#8-#3, (275)

3/8

continued