Parallel redundant system description – Powerware 9315 User Manual

Page 34

Advertising
background image

28

Powerware 9315 Parallel Redundant System I & O

164202013, Rev. D 041599

Parallel Redundant System Description

The parallel redundant system consists of two identical UPS modules, a parallel

cabinet, and one or two battery racks or cabinets.
The parallel cabinet consists of two module output breakers designated MOB 1

and MOB 2. These output breakers receive power input from the AC output of the

UPS modules. If one UPS module becomes disabled, it trips off, leaving the

redundant UPS module to continue to supply power to the critical load. The

primary function of the MOBs is to allow isolation of a module for maintenance or

service. In a parallel redundant system the redundant module becomes the

system’s maintenance bypass source.
There are two lamps located on the inside of the parallel cabinet labeled

OK TO CLOSE. When one of these lamps illuminates, the corresponding MOB

can be closed. It is important to note that it is only safe to close the MOBs when

the

OK TO CLOSE indicator lights are illuminated. A LAMP TEST pushbutton is

located inside the parallel cabinet for testing these indicators. The parallel cabinet

also includes associated terminal strips for making the power and control

connections to UPS modules. Figure 10 shows the controls and indicators of the

parallel cabinet.

Advertising