Module output breakers (mobs), How to open and close the mob – Powerware 9315 User Manual

Page 41

Advertising
background image

35

Powerware 9315 Parallel Redundant System I & O

164202013 Rev. D 041599

Operating Instructions for

the Parallel Redundant System

The following procedures are for the operation of UPS modules in parallel. After

installation of the parallel redundant system, the UPS modules run in parallel with

each other.

Module Output Breakers (MOBs)

The parallel cabinet contains two MOBs labeled MOB 1 and MOB 2. The UPS

modules should be labeled in accordance with which MOB it is connected (e.g.,

MOB 1 should be wired to UPS 1).
When both MOB 1 and MOB 2 are closed, each UPS module operates as part of a

parallel system. When one MOB is open, the redundant UPS module continues to

support the critical load. The redundant UPS module acts as a single stand-alone

system.

How to Open and Close the MOB

CAUTION:

Improper operation of these circuit breakers can cause the loss of the critical

bus (output) or damage equipment.

Close the MOB only when its designated

OK TO CLOSE lamp is illuminated.

A UPS module’s designated MOB, MOB 1 or MOB 2, may be opened if the MOB

for the redundant module is closed and its

OK TO CLOSE lamp is illuminated.

Refer to

How to Isolate a Module in this chapter for information on when a module’s

designated MOB can be opened.

Starting and Stopping Using Parallel Redundant System

Start each module as described for normal UPS system startup in the

PowerwareÒ

9315 Operation manual provided with the UPS system. If the MOBs have been

opened, they should only be closed when the

OK TO CLOSE lamp is illuminated.

The following descriptions give details on starting in modes, turning the module off,

and using the

LOAD OFF pushbutton.

Advertising