3 troubleshooting guide – Panasonic CW-XC244HU User Manual

Page 19

Advertising
background image

—19—

4.3 TROUBLESHOOTING GUIDE

In general, possible trouble is classified in two causes.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.

Unit runs but poor cooling

Ineffective Cooling

Check of outdoor coil
(heat exchanger) & the fan
operation.

Check gas leakage.

Repair gas leak.

Satisfactory operation with
temperature difference of
inlet & outlet air ; 44.6~50

°

F

Check heat load increase.

Unexpected residue

Overloaded Circuit

Malfunction of compressor

Replacement of
compressor

Check of cold air circulation
for smooth flow.

Dirty indoor coil
(Heat exchanger)

Malfunction of fan

Clogged of air filter

Obstruction at air outlet

Correct above trouble

Stop of auto air-swing

Check clogging in
refrigeration circuit.

Repair clogging in
refrigeration circuit.

Discharte all of gas from
refrigeration sycle and
recharge the rated amount
of refrigerant.