1.1 SAFETY PRECAUTIONS

1. When servicing, set the POWER of CONTROL BOARD

to Off and unplug the power cord.

2. Observe the original lead dress.

If a short circuit is found, replace all parts which have
been overheated or damaged by the short circuit.

3. After servicing, make an insulation resistance test to

prevent the customer's exposure to shock hazards.

1.2 INSULATION RESISTANCE TEST

1. Unplug the power cord and connect a jumper between

2 pins (black and white).

2. The grounding conductor (green or green and yellow) is

to be open.

3. Measure the resistance value with an ohm meter between

the jumpered lead and each exposed metallic part on the
equipment.

4. The value should be over 1 M

.

1. PREFACE

This service manual provides various service information, including the mechanical and electrical parts, etc.
This room air conditioner was manufactured and assembled under a strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.

1.3 SPECIFICATIONS

* DB:Dry Bulb ** WB:Wet Bulb
NOTE : Specifications are subject to minor change without notice for further improvement.

CW-XC184HU

CW-XC244HU

POWER SUPPLY

Ø, V, Hz

COOLING CAPACITY

Btu/h.

POWER INPUT

W

RUNNING CURRENT

A

EER

Btu/h.W

REFREIGERANT (R-22) CHARGE

OPERATING INDOOR

°F(°C)

TEMPERATURE OUTDOOR

°F(°C)

EVAPORATOR

CONDENSER

FAN

INDOOR

OUTDOOR

FAN SPEED

FAN/COOLING

FAN MOTOR

OPERATION CONTROL

ROOM TEMP. CONTROL

AIR DIRECTION

VERTICAL

CONTROL

HORIZONTAL

CONSTRUCTION

PROTECTOR

COMPRESSOR

FAN MOTOR

POWER CORD

DRAIN SYSTEM

NET WEIGHT

lbs(kg)

DIMENSION(W*H*D)

inch(mm)

1, 208/230, 60

17,800/17,300

23,500/23,000

1,660/1,620

2,500/2,450

7.4/7.9

11.2/12.0

10.7/10.7

9.4/9.4

780g (27.5 oz)

980g (34.6oz)

DB : 80(26.7) WB : 67(19.4)

DB : 95(35) WB : 75(23.9)

3 ROW 15 STACKS, SLIT-FIN TYPE

2 ROW 19 STACKS, LOUVERED-FIN TYPE

TURBO FAN

PROPELLER TYPE FAN WITH SLINGER-RING

3/3

6 POLES

REMOTE CONTROL

THERMISTOR

MANUAL

AUTO

SLIDE IN-OUT CHASSIS

INTERNAL OVERLOAD PROTECTOR

INTERNAL THERMAL PROTECTOR

1.6m(63") (3WIRE WITH GROUNDING)

ATTACHMENT PLUG(CORD-CONNECTED TYPE)

DRAIN PIPE OR SPLASHED BY FAN SLINGER

123(55)

146(66)

26 * 16

27

/

32

* 26

17

/

32

(660 * 428 * 675)

26 * 16

27

/

32

* 30

17

/

32

(660 * 428 * 770)

MODELS

ITEMS