6

OEM6250 Installation Guide

Serial Communication

RS-232C Connections

LIMITS

RP240

9

5

1

9

1

49

50

Rx
Tx
GND
SHLD

1

Tx
Rx
GND

NOTE: Max. cable length is 50 ft (15.25 m)

AUX

1

7
1

9

25-Pin COM Port:

9-Pin COM Port:

Serial Port Connection

Pin 2 (Rx)

Pin 3 (Tx)

Pin 5 (GND)

Pin 2 (Tx)

Pin 3 (Rx)

Pin 7 (GND)

Rx
Tx
GND

Rx
Tx
GND

RS-232C Daisy-Chain Connections *

Rx
Tx
GND
SHLD

Rx
Tx
GND
SHLD

Unit 0

Unit 1

Unit 2

Tx
Rx
GND

Daisy Chain to a Computer or Terminal

Stand-Alone Daisy Chain

Be sure to set unique devices addresses for each unit.
To set the address, use the DIP switch (see below),
or use the

ADDR

command (see

6000 Series Software Reference

).

*

Rx
Tx
GND
SHLD

Rx
Tx
GND
SHLD

Rx
Tx
GND
SHLD

Unit 0

Unit 1

Unit 2

Rx
Tx
GND
SHLD

Changing the address and baud rate (OPTIONAL)

Factory Settings
May Be Sufficient

• Device address is

set to zero (if you
are connecting
multiple units in a
daisy-chain, you
can automatically
establish the device
address by using
the

ADDR

command).

• Factory default

baud rate is 9600.

N

O

1234

DIP Switch

Factory Default Setting Shown

OEM6250

Switch #1

Switch #2

Switch #3

Device Address

To implement the Auto Baud feature:

Switch #4 ON = Auto Baud Enabled
Switch #4 OFF = Auto Baud Disabled (default)

The default baud rate is 9600. As an alternative, you can use
this procedure to automatically match your terminal's speed
of 1200, 2400, 4800, or 9600 baud.

1. Set switch 4 to ON.

2. Connect the OEM6250 to the terminal.

3. Power up the terminal.

4. Cycle power to the OEM6250 and immediately press the

space bar several times.

5. The OEM6250 should send a message with the baud rate

on the first line of the response. If no baud rate message
is displayed, verify steps 1-3 and repeat step 4.

6. Change switch 4 to OFF.

7. Cycle power to the OEM6250. This stores the baud rate

in non-volatile memory.

NOTE: If Auto Baud is enabled, the OEM6250 performs its
auto baud routine every time it is powered up or reset. The
OEM6250 is only capable of matching 1200, 2400, 4800, and
9600 baud. Once the baud rate has been determined, the
OEM6250 stores that baud rate in non-volatile memory;
therefore, Switch #4 should be set to the OFF position after
the baud rate has been determined.

ADDRESS

AUTO BAUD

OFF

OFF

OFF

Ø

(default)

ON

OFF

OFF

1

OFF

ON

OFF

2

ON

ON

OFF

3

OFF

OFF

ON

4

ON

OFF

ON

5

OFF

ON

ON

6

ON

ON

ON

7

* Device address is checked upon power up or reset.