Parker Hannifin SERVO CONTROLLER OEM6250 User Manual

Page 23

Advertising
background image

Chapter 1. Installation

1 7

INPUT CONNECTIONS

Connecting to electronic devices such as PLCs

Connection to a
Sinking Output
D e v i c e

Connection to a
Sourcing Output
D e v i c e

Connection to a
Combination of
Sinking &
Sourcing
O u t p u t s

Electronic

Device

Out 5-24 Volts

GND

74HCxx

6.8 K

W

47 K

W

Input

Connection

Ground

Connection

Output

Ground

IN-P

+5V

GND

Pulled up

to +5V

(sourcing)

The output should
be able to sink at
least 1mA of current.

OEM6250

GND

+5VDC

R12

(0 K

W

)

Remove if you wish
to use an external
5-24V power source.

Electronic

Device

Out 5-24 Volts

GND

74HCxx

47 K

W

Input

Connection

Ground

Connection

Output

Ground

IN-P

+5V

GND

Pulled

down to

ground

(sinking)

OEM6250

GND

V1

R1

+5VDC

R12

(0 K

W

) is

removed.

6.8 K

W

Electronic

Device

Out 5-24 Volts

GND

74HCxx

47 K

W

Input

Connection

Ground

Connection

Output

Ground

IN-P

+5V

GND

OEM6250

GND

V1

R1

R

+5VDC

R12

(0 K

W

)

Remove if you wish
to use an external
5-24V power source.

6.8 K

W

Pulled up

to +5V

(sourcing)

The value of R must be < 6.8 K

W

and sized such that V

A

< 1.0V when the output is

open and V

A

> 3.4V when the output is closed.

R

1

must be < R. If R

1

is 0

W

, the typical value for R is 450

W

.

V

A

PROGRAMMING TIP

Connecting to a
sinking output?
Set the
input’s active level to low
with the

INLVL

command

(

¯

= active low).

Connecting to a
sourcing output?
Set
the input’s active level to
high with the

INLVL

command (

1

= active high).

Thus, when the output is
active, the

TIN

status

command will report a “

1

(indicates that the input is
active), regardless of the
type of output that is
connected.

Details on setting the active
level and checking the input
status are provided in the
6000 Series Programmer’s
Guide. Refer also to the

INLVL

and

TIN

command

descriptions in the

6000

Series Software Reference.

NOTE: If you will be connecting to a combination of sourcing and sinking outputs, leave

IN-P

internally connected to

+5V

(or remove R12 and connect

IN-P

to an external 5-24VDC supply)

to accommodate sinking output devices. Then for each individual input connected to a
sourcing output, wire an external resistor between the OEM6250’s programmable input
terminal and ground (see “R” in above drawing). The resistor provides a path for current to
flow from the device when the output is active.

Advertising