Ani ]network analog input voltage status, Network analog input voltage status – Parker Hannifin GEM6K User Manual

Page 38

Advertising
background image

[ \ANI ]

Network Analog Input Voltage Status

Type:

Network; Assignment or Comparison

Product Rev

Syntax:

n\mANI.i (see example below)

Units:

n = network server #
m = module #
i = analog input # on module “m”

Range:

n = 1-6
m = 0-7
j = 1-2

Default:

n/a

Response:

n/a

See Also:

NTIO, \TANI, \TIO, VAR

6K 5.3

Use the

\ANI

operand to assign the voltage level of an OPTO22 analog input to a real variable (

VAR

), or to make a

comparison against another value.

Syntax:

VARx=

n\mANI.i

where “

n

” is the network server number of the OPTO22 unit, “

m

” is the I/O module number,

and “

i

” is the input/channel number on the module (e.g.,

VAR3=2\1ANI.1

assigns the voltage at analog input 1

on module 1 of OPTO22 server 2 to

VAR3

). The

\ANI

operand can also be used in a condition expression such as

IF(2\3ANI.1>=2.0)

or

WAIT(2\4ANI.1<=1.5)

.

The controller addresses the OPTO22 I/O locations as follows:

Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.

Digital

Input

Module

Input

1

0

Input

2

Input

3

Input

4

Digital

Input

Module

Input

1

1

Input

2

Input

3

Input

4

Digital

Output

Module

Output

1

2

Output

2

Output

3

Output

4

Digital

Output

Module

Output

1

3

Output

2

Output

3

Output

4

Analog

Output

Module

Output

1

4

Output

2

Analog

Output

Module

Output

1

5

Output

2

Analog

Input

Module

Input

1

6

Input

2

Analog

Input

Module

Input

1

7

Input

2

EXAMPLE: OPTO22 is Network Server #2

2\0IN.3

2\3OUT.2

2\5ANO.1

2\7ANI.2

Example:
2NTIP2,172,54,125,34 ; Identify network server #2 as an OPTO22 unit at IP address

; 172.54.125.34

2NTCONN1

; Attempt a connection to network server #2 (OPTO22 unit)

2\6NTIO3

; Server #2 (OPTO22), module #6 is an analog input module

2\7NTIO3

; Server #2 (OPTO22), module #7 is an analog input module

WAIT(2\6ANI.1<=+1.5) ; Wait until the voltage at analog input #1 of module #6 on

; Server #2 (OPTO22) is less than or equal to +1.5VDC

IF(2\7ANI.2>+2.4)

; If the voltage at analog input #2 of module 7 on Server #2
; (OPTO22) is greater than +2.4 VDC ...

page 34