Tintransfer network digital input status, Tiotransfer ethernet i/o status, Tin transfer – Parker Hannifin GEM6K User Manual

Page 46: Network, Digital input status, Tio transfer, Ethernet i/o status, Transfer network digital input status, Command (e.g, Transfer ethernet i/o status

Advertising
background image

\TIN

Transfer Network Digital Input Status

Type:

Network; Transfer

Product Rev

Syntax:

<!>n\mTIN<.i>

Units:

n = network server #
m = module #
i = digital input # on module “m” (for bit-select operation)

Range:

n = 1-6
m = 0-7
i = 1-4

Default:

n/a

Response:

1\1TIN:
1\1TIN.2:

*1100
*1

See Also:

[ \IN ], NTIO, \TIO

6K 5.3

The

\TIN

command returns the current status (active/on or inactive/off) of the network digital inputs. Each module of

digital inputs has its own unique

\TIN

response. The network server number and module number must precede the

\TIN

command (e.g.,

2\3TIN

reports the status of all digital inputs on module 3 of network server 2).

If the status of a specific input is required, use the bit select operator (.). For example,

1\3TIN.2

reports the status of input

2 on module 3 of network server 1.

The controller addresses the OPTO22 I/O locations as follows:

Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.

Digital

Input

Module

Input

1

0

Input

2

Input

3

Input

4

Digital

Input

Module

Input

1

1

Input

2

Input

3

Input

4

Digital

Output

Module

Output

1

2

Output

2

Output

3

Output

4

Digital

Output

Module

Output

1

3

Output

2

Output

3

Output

4

Analog

Output

Module

Output

1

4

Output

2

Analog

Output

Module

Output

1

5

Output

2

Analog

Input

Module

Input

1

6

Input

2

Analog

Input

Module

Input

1

7

Input

2

EXAMPLE: OPTO22 is Network Server #2

2\0TIN.3

2\3TOUT.2

2\5TANO.1

2\7TANI.2

\TIO

Transfer Ethernet I/O status

Type:

Network; Transfer

Product Rev

Syntax:

<!>n\TIO

Units:

n = network server #

Range:

n = 1-6

Default:

n/a

Response:

(see example below)

See Also:

NTIO, \TANI, \TANO, \TIN, \TOUT

6K 5.3

The

\TIO

command displays the status of the current I/O configuration for the specified OPTO22 network server. If a

module is not configured (with the

NTIO

command), it will not be included in the report. A digital I/O module has 4 points

and an analog I/O module has 2.

Example Response:

>1\TIO
*SERVER 1
* Module Type Status
* 0 DIGITAL INPUTS 1011

page 42

Advertising
This manual is related to the following products:

6K