Control over Polling: If you want to stop the 6K from writing binary data to the PLC, but continue to exchange

NTMPRI

,

NTMPWI

and

NTMPRB

data, use the

NTMPWBi,i,0,i

command. If you need to stop polling all mapped variables, use the

nNTPOLL0

command.

Example:
2NTIP1,172,54,125,34

; Identify network server #2 as an Allen-Bradley PLC at
; IP address 172.54.125.34

2NTCONN1

; Attempt connection to network server #2

2NTMPWB3,0,15,20

; File 3, elements 0-14, in the AB PLC are mapped to
; the 6K's binary variables VARB20-VARB34

2NTPOLL50

; Start polling network server #2, set interval to 50 ms

VARB25 = b1111000011110000

; The value of AB file 3, element 5, will be set to
; 111000111000, because it is mapped to VARB25

NTMPRI

Network Map Integer Variables for Reading from PLC

Type:

Network

Product Rev

Syntax:

<!><n>NTMPRI<i>,<i>,<i>,<i>

Units:

n = network server #
1

st

i = Allen Bradley data file #

2

nd

i = # of the 1

st

element in data file (beginning of range)

3

rd

i = # of the elements to include in range

4

th

i = # of the 1

st

integer (VARI) variable in the 6K to map to

Range:

n = 1-6
1

st

i = 0-n (n depends on size of file)

2

nd

i = 0-n (n depends on size of file)

3

rd

i = 0 or 1-50 (0 disables polling for this mapping only)

4

th

i = 1-225

Default:

1NTMPRI0,0,0,0 (no mapping)

Response:

1NTMPRI: *1NTMPRI1,5,15,23

See Also:

NTCONN, NTIP, NTMPRB, NTMPWB, NTMPWI, NTPOLL, [ NTS ], NTSELP,
TNTS, TNTSF, VARI

6K 5.3

<n>

NTMPRI

<i>,<i>,<i>,<i>

Network Server #

Range: 1-6

# of Allen-Bradley data file

# of first element in AB data file
(beginning of range)

# of elements in range
# of first integer variable (
VARI) in 6K

(beginning of range, max value is 225)

EXAMPLE:

IF:

• Allen-Bradley PLC is server #2

• The PLC’s integer data file 9 has 30

elements. Use data elements 15-29
(15 elements total) for integer data
that is to be shared with the 6K.

• Use the 6K’s integer variables 35-49

(15 variables total) to store the data
from the PLC.

The required mapping command is:

2NTMPRI9,15,15,35

The

NTMPRI

command maps a range of integer data elements from the AB PLC to a range of integer (

VARI

) variables in

the 6K. There are 225

VARI

variables available in the 6K for storing integer data. To perform an integer data read from the

PLC:

1. Assign the AB PLC a server number, according to its IP address (

NTIP

command).

2. Connect to the AB PLC, according to its server number (

NTCONN

command).

3. Map a range of integer elements in the AB PLC to a range of integer (

VARI

) variables in the 6K (

NTMPRI

command).

4. Start polling the AB device at a specific polling interval (

NTPOLL

command). This updates the 6K integer (

VARI

)

variables with the integer element data from the AB PLC. You can then use the PLC integer data (via the

VARI

variables) in conditional expressions, command value substitutions and variable assignments.

Saved in Non-Volatile Memory

This command is saved in the controller’s non-volatile memory, and is remembered on power-up
and RESET.