3.2.3 Bonding the Power Center

Install a bonding lug to the Power Center
enclosure. Connect the bond lug, using a #8 solid
copper core wire, to an approved earth ground (an
approved ground stake, grid, or conducting metal
water pipe buried to a sufficient depth). See
Figure 3.

3.2.2 3HP (Standard) Relays

For each piece of 240 volt equipment to be
controlled, connect line power to the two (2) line
terminals
and connect equipment power to the two
(2) load terminals
on the same relay.

For each piece of 120 volt equipment, connect
power to a line terminal
and connect equipment to
a load terminal
on the same relay.

NOTE The following are the contact ratings for 3HP

(Standard) Relay. DO NOT exceed any ratings.
3 HP @ 240 VAC; 1½ HP @ 120 VAC; 25
Amps; 1500 Watts.

Figure 3.

Standard Power Center - Bonding

Bonding Lug

Earth

Ground

Breaker

Panel

Blower

(120 VAC)

Filter Pump

(240 VAC)

Primary

24 V

AC

T

ransformer