Pelco Universal Keyboard KBD300A User Manual

Page 17

Advertising
background image

Pelco Manual C527M-L (3/04)

[ 17 ]

RS-422 Interface (CM6700)

Refer to Figure 6.

Remove the cover from the CM6700 SCU and verify that the DIP switches for COM 2 are set for
RS-422. Refer to the

COM 2 Port section in the CM6700 Installation/Operation Manual for setting the

switches. Reinstall the cover.

ᕢ Use an existing CM6700 keyboard to program the COM 2 communication port. (If there is no other

keyboard, use the one you are installing. Set all DIP switches OFF and plug the keyboard into the Lo-
cal Keyboard port on the back of the CM6700. Remove when programming is completed.) Refer to the
Setting COM 2 Communication Parameters section in the CM6700 Installation/Operation Manual for
programming instructions. Set COM 2 port parameters as follows:

Baud: 9600, Parity: Odd, Stop Bits: 1

Decide on a suitable location for the keyboard and wall block. The keyboard must be within 25 feet
(7.6 meters) of the wall block. The wall block must be within 6 feet (1.8 m) of the nearest suitable
electrical outlet. Do not mount the wall block at this time.

Remove the wall block cover and make connections between the wall block and COM 2 of the
CM6700 SCU.

At the wall block wire the transformer to pins 3 and 4. Polarity is unimportant.

Replace the cover on the wall block. A double-sided sticky pad is provided to mount the wall block.
Secure the wall block to a suitable surface.

Set the keyboard DIP switches according to the instructions in the

Switch Settings section.

Plug in the keyboard data cable.

Plug the KBDKIT or KBDKIT-X transformer into a suitable outlet.

ᕫᕾ

Apply power to the CM6700 (if not already powered). To initialize the keyboard, wait five seconds
after power-up, enter the number for the monitor you are viewing (1-4), and press MON. The LED dis-
play shows the number entered.

ᕫᕵ

Once you apply power to the keyboard and the CM6700 SCU, you can use the keyboard in the same
manner as a normal keyboard except that in ASCII Mode you cannot program the CM6700.

ᕫᕶ

Go to the

Programming and Operation section and program and test for proper operation.

Advertising