4.4.4.4 TYPE MX341 AVR

The following 'jumper' connections on the AVR should be
checked to ensure they are correctly set for the generating set
application.

Refer to Fig. 4 for location of setting links.


1. Frequency selection terminals

50Hz operation LINK 2-3

60Hz operation LINK 1-3


2. Stability selection terminals

Frame UC22 LINK A-C

Frame UC27

LINK B-C


3. Sensing selection terminals *

LINK

2-3

LINK

4-5

LINK

6-7


4. Excitation Interruption Link

LINK

K1-K2



Fig. 4

4.4.4.5 TYPE MX321 AVR


The following 'jumper' connections on the AVR should be
checked to ensure they are correctly set for the generating set
application.

Refer to Fig. 5 for location of setting links.

Fig. 5


1. Frequency selection terminals

50Hz operation

LINK 2-3

60Hz operation

LINK 1-3


2. Stability selection terminals

Frame UC22

LINK A-C

Frame UC27

LINK B-C


3. Terminals K1 - K2

Excitation circuit breaker closed.
If this option not fitted, K1 - K2 linked at auxiliary terminal
block.