It is possible that simply running the gen set unexcited – AVR
terminals K1 K2 open circuit - for a period of say 10 minutes
will sufficiently dry the surface of the windings and raise the IR
sufficiently, to greater than 1.0 M

Ω , and so allow the unit to

be put into service.