7.4.2 SX440 AVR - FAULT FINDING

No voltage

build-up when

starting set

1. Check link K1-K2 on auxiliary

terminals.

2. Check

speed

3. Check residual voltage. Refer to

subsection 7.4.7.

4. Follow Separate Excitation Test

Procedure to check generator and
AVR. Refer to subsection 7.5.

Unstable voltage

either on no-load

or with load

1. Check speed stability.
2. Check stability setting. Refer to

subsection 4.6.

High voltage

either on no-load

or with load

1. Check

speed.

2. Check that generator load is not

capacitive (leading power factor).

Low voltage

no-load

1. Check

speed.

2. Check link 1-2 or external hand

trimmer leads for continuity.

Low voltage

on-load

1. Check

speed.

2. Check UFRO setting. Refer to

subsection 4.7.1.1.

3. Follow

Separate

Excitation

Procedure to check generator and
AVR. Refer to subsection 7.5.

7.4.3 SX421 AVR - FAULT FINDING

No voltage

build-up when

starting set

1. Check circuit breaker ON. Refer to

subsection 6.4.1.

2. Check

speed

3. Check residual voltage. Refer to

subsection 7.4.7.

4. Follow Separate Excitation Test

Procedure to check generator and
AVR. Refer to subsection 7.5.

Unstable voltage

either on no-load

or with load

1. Check speed stability.
2. Check stability setting. Refer to

subsection 4.6.

High voltage

either on no-load

or with load

1. Check

speed.

2. Check link 1-2 or external hand

trimmers leads for continuity. Check
continuity of leads 7-8 and P3-P2 for
continuity.

3. Check that generator load is not

capacitive (leading power factor).

Low voltage

no-load

1. Check

speed.

2. Check link 1-2 or external hand

trimmer leads for continuity.

Low voltage

on-load

1. Check

speed.

2. Check UFRO setting. Refer to

subsection 4.7.1.1.

3. Follow

Separate

Excitation

Procedure to check generator and
AVR. Refer to subsection 7.5.

Excessive

voltage/speed

dip on load

switching

1. Check governor response.
2. Refer to generating set manual.

Check ‘DIP’ setting. Refer to
subsection 4.7.1.4.









7.4.4 TRANSFORMER CONTROL - FAULT FINDING


No voltage

build-up when

starting set

1. Check

transformers

rectifiers.

2. Check transformer secondary

winding for open circuit.

Low voltage

1. Check

speed.

2. Check transformer air gap setting.

Refer to subsection 4.7.2.

High voltage

1. Check

speed.

2. Check transformer air gap setting.

Refer to subsection 4.7.2.

3. Check transformer secondary

winding for open circuit.

Excessive

voltage/speed

dip on load

switching

1. Check speed drop on-load.
2. Check

transformers

rectifiers.

3. Check transformer air gap setting.

Refer to subsection 4.7.2.