PI Manufacturing AC generators User Manual

Page 26

Advertising
background image


Ground V and W phase and megger U phase to ground
Ground U and W phase and megger V phase to ground
Ground U and V phase and megger W phase to ground

If the minimum value of 1.0M

Ω is not obtained, drying out

must be continued and the test repeated.

7.2 BEARINGS


All bearings are supplied sealed for life and are, therefore, not
regreasable.

Important ! The life of a bearing in service is subject to

the working conditions and the
environment.


Important ! Long stationary periods in an environment

where there is vibration can cause false
brinnelling which puts flats on the ball and
grooves on the races. Very humid
atmospheres or wet conditions can emulsify
the grease and cause corrosion.


Important

!

High axial vibration from the engine or

misalignment of the set will stress the
bearing.


The bearing, in service, is affected by a variety of factors that
together will determine the bearing life. We recommend that
the health of the bearings be monitored, using ‘spike energy’
vibration monitoring equipment. This will allow the timely
replacement of bearings, that exhibit a deteriorating trend,
during a major engine overhaul.

If excessive heat, noise or vibration is detected, change the
bearing as soon as practicable. Failure to do so could result in
bearing failure.

In the event that ‘spike energy’ vibration monitoring equipment
is not available, it is strongly recommend that consideration
be given to changing the bearing during each ‘major engine
overhaul’.

Belt driven application will impose an additional load on
bearings. The bearing life will therefore be significantly
affected. It is important that the side load limits given in
SECTION 3 are not exceeded and the health of the bearing is
monitored more closely.

7.3 AIR FILTERS


The frequency of filter maintenance will depend upon the
severity of the site conditions. Regular inspection of the
elements will be required to establish when cleaning is
necessary.

7.3.1 CLEANING PROCEDURE


Removal of filter elements enables access
to LIVE parts. Only remove elements with
the generator out of service.




Remove the filter elements from the filter frames. Immerse or
flush the element with a suitable detergent until the element is
clean. Dry elements thoroughly before refitting.






7.4 FAULT FINDING


Important

!

Before commencing any fault finding

procedure examine all wiring for broken or
loose connections.


Four types of excitation control system, involving four types of
AVR, can be fitted to the range of generators covered by this
manual. The systems can be identified by a combination of
AVR type, where applicable, and the last digit of the generator
frame size designation. Refer to the generator nameplate then
proceed to the appropriate subsection as indicated below :-

DIGIT

EXCITATION CONTROL

SUBSECTION

6

SX460 AVR

7.4.1

4

AS440 AVR

7.4.2

4

7.4.3

5

Transformer control

7.4.4

3

MX341 AVR

7.4.5

3

MX321 AVR

7.4.6


7.4.1 SX460 AVR - FAULT FINDING

No voltage

build-up when

starting set

1. Check

speed

2. Check residual voltage. Refer to

subsection 7.4.7.

3. Follow Separate Excitation Test

Procedure to check generator and
AVR.

Unstable voltage
either on no-load

or with load

1. Check

speed

stability.

2. Check stability setting. Refer to

subsection 4.6.

High voltage

either on no-load

or with load

1. Check

speed.

2. Check that generator load is not

capacitive (leading power factor).

Low voltage

no-load

1. Check

speed.

2. Check link 1-2 or external hand

trimmer leads for continuity.

Low voltage

on-load

1. Check

speed.

2. Check UFRO setting. Refer to

subsection 4.7.1.1.

3. Follow

Separate

Excitation

Procedure to check generator and
AVR. Refer to subsection 7.5.


Danger !

Advertising