7.4.5 MX341 AVR - FAULT FINDING

No voltage

build-up when

starting set

1. Check link K1-K2 on auxiliary

terminals

2. Follow Separate Excitation Test

Procedure to check machine and
AVR. Refer to subsection 7.5.

Loss of voltage

when set runninig

1. First stop and restart set. If no

voltage or voltage collapses after
short time, follow Separate Excitation
Test Procedure. Refer to subsection
7.5.

Generator

voltage high

followed by

collapse

1. Check sensing leads to AVR.
2. Refer to Separate Excitation Test

Procedure. Refer to subsection 7.5.

Voltage unstable,

either on no-load

or with load

1. Check speed stability.
2. Check “STAB” setting. Refer to Load

Testing section for procedure. Refer
to subsection 4.6.

Low voltage

on-load

1. Check

speed.

2. If correct check “UFRO” setting.

Refer to subsection 4.7.1.1.

Excessive

voltage/speed

dip on load

switching

1. Check governor response. Refer to

generating set manual. Check “DIP”
setting. Refer to subsection 4.7.1.4.

Sluggish

recovery on load

switching

1. Check governor response. Refer to

generating set manual.


































7.4.6 MX321 AVR - FAULT FINDING

No voltage

build-up when

starting set

1. Check link K1-K2 on auxiliary

terminals. Follow Separate Excitation
Test Procedure to check machine
and AVR. Refer to subsection 7.5.

Voltage very slow

to build up

1. Check setting of ramp potentiometer.

Refer to 4.7.1.5.

Loss of voltage

when set running

1. First stop and restart set. If no

voltage or voltage collapses after
short time, follow Separate Excitation
Test Procedure. Refer to subsection
7.5.

Generator

voltage high

followed by

collapse

1. Check sensing leads to AVR.
2. Refer to Separate Excitation Test

Procedure. Refer to subsection 7.5.

Voltage unstable,

either on no-load

or with load

1. Check

speed

stability.

2. Check “STAB” setting. Refer to Load

Testing section for procedure. Refer
to subsection 4.6.

Low voltage

on-load

1. Check

speed.

2. If correct check “UFRO” setting.

Refer to subsection 4.7.1.1.

Excessive

voltage/speed dip

on load switching

1. Check governor response. Refer to

generating set manual. Check “DIP”
setting. Refer to subsection 4.7.1.4.

Sluggish

recovery on load

switching

1. Check governor response. Refer to

generating set manual. Check
“DWELL” setting. Refer to Load
Testing section 4.7.1.4.