Chapter 5: Alarm Programming

53

In another example, input 2 is configured as a temperature
input. The current temperature is 76 degrees. During a Status
Report:

If disabled, the Model 1104 recites, “Number 2—Off

76 degrees—OK.”

If enabled, the Model 1104 recites, “Number 2—

76 degrees—OK.”

5.3 Input Recognition Time

The Input Recognition Time is the length of time an alert
condition must be present before a valid alarm exists and dial-
out is activated. This time period is programmable, from 0
minutes, 0 seconds (for immediate response) up to a period of
272 minutes, 0 seconds. If an alert condition begins and then
clears within the established Recognition Time, no dial-out will
occur. When an alert condition continues beyond the
programmed Recognition Time, the Model 1104 initiates dial-
out. The default setting for Input Recognition Time is 0
minutes, 3 seconds.

5.3.1 Programming Input Recognition Time

1.

Press SET.

2.

Press RECOGNITION TIME.

3.

Press the number (1 to 4) of the selected input to be
programmed.

The Model 1104 responds: “Enter minutes.”