Floor construction – NEC EXPRESS800 User Manual

Page 21

Advertising
background image

Planning Your Site 2-5

Floor Construction

Aspects of floor construction, such as load capacity and construction materials,
must be considered when installing one or more rack systems.

Note: The rack supports up to 551.2 lbs. (250 kg).

Use Table 2-1 to calculate the load that each rack of your system configuration
places on the floor.

Table 2-1. Equipment Weight

Component

Weight
(approx.)

Number
Installed

Total

System Rack (42u)

253 lbs.
(114.8Kg.)

Express5800/120Ld

66.1 lbs.
(30.0Kg.)

Express5800/120Mc2

66.1 lbs.
(30.0Kg.)

Express5800/120Mc3

66.1 lbs.
(30.0Kg.)

Express5800/180Ra-7

165 lbs.
(75.0Kg.)

Express5800 ES1400

38.0 lbs.
(17.2Kg.)

Express5800 HX4500

207 lbs.
(94.0Kg.)

Express5800 HX4600

170 lbs.
(77.0Kg.)

Express5800 HV8600

165 lbs.
(75.0Kg)

Express5800 LC1400

65.0 lbs.
(29.3Kg.)

Express5800 LS2400

38.0 lbs.
(17.2Kg.)

Express5800 MC2200

65.0 lbs.
(29.3Kg.)

Express5800 MC2400

65.0 lbs.
(29.3Kg.)

Express5800 MH4500

99.2 lbs.
(45.0Kg.)

3U Disk Expansion Unit (3UDEU)

44 lbs.
(20.0Kg)

UPS

112.0 lbs.
(50.8Kg.)

PDU

9.0 lbs.
(4.08Kg.)

Monitor

Concentrator

10 lbs.
(4.5Kg.)

Total

Advertising