Table 6. vent table – Nordyne Downflow Condensing Furnace M3RL User Manual

Page 15

Advertising
background image

15

*NOTES
1.

Subtract 3.5 ft. for each additional 3" 90 degree elbow.

2.

Two 45 degree elbows are equivalent to one 90 degree elbow.

3.

One short radius elbow is equivalent to two long radius
elbows.

4.

Do not include termination elbows in calculation of vent length.

5.

This table is applicable for elevations from sea level to 4000
ft. For higher elevations, decrease vent pipe lengths by 8% per
1000 ft. of altitude.

6.

Only the above pipe materials are approved for use with these
condensing furnaces.

PVC,CPVC or ABS

Inlet/Outlet

SCH. 40 Pipe Size

3"

3"

Model M3RL 060

50

50

Model M3RL 080

50

50

APPLICATION

MAXIMUM

DIRECT VENT, DUAL

PIPE LENGTH (ft.)*

Table 6. Vent Table

VENT TERMINAL

AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

1

In accordance with the current CSA B149.1

Natural Gas and Propane Installation Code

2

In accordance with the current ANSI Z223.1 / NFPA 54

National Fuel Gas Code

† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family

dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
*

For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA B149.1, the following statement shall be included:

“Clearance in accordance with local installation codes, and the requirements of the gas supplier and the

manufacturer’s installation instructions.”

Canadian Installations

1

US Installations

2

A = Clearance above grade, veranda, porch,

deck, or balcony

12 inches (30 cm)

12 inches (30 cm)

B = Clearance to window or door that may be

opened

6 inches (15 cm) for appliances

10,000

Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (3 kW) and

100,00 Btuh (30 kW), 36 inches (91 cm) for
appliances >100,00 Btuh (30 kW)

6 inches (15 cm) for appliances

10,000

Btuh (3 kW), 9 inches (23 cm) for
appliances > 10,000 Btuh (3 kW) and

50,000 Btuh (15 kW), 12 inches (30 cm) for
appliances > 50,000 Btuh (15 kW)

C = Clearance to permanently closed window

*

*

D = Vertical clearance to ventilated soffit

located above the terminal within a
horizontal distance of 2 feet (61 cm) from
the center line of the terminal

*

*

E = Clearance to unventilated soffit

*

*

F = Clearance to outside corner

*

*

G = Clearance to inside corner

*

*

H = Clearance to each side of center line

extended above meter/regulator assembly

3 feet (91 cm) within a height 15 feet
above the meter/regulator assembly

*

I = Clearance to service regulator vent outlet

3 feet (1.83 m)

*

J = Clearance to nonmechanical air supply inlet

to building or the combustion air inlet to any
other appliance

6 inches (15 cm) for appliances

10,000

Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (3 kW) and

100,00 Btuh (30 kW), 36 inches (91 cm) for
appliances >100,00 Btuh (30 kW)

6 inches (15 cm) for appliances

10,000

Btuh (3 kW), 9 inches (23 cm) for
appliances > 10,000 Btuh (3 kW) and

50,000 Btuh (15 kW), 12 inches (30 cm) for
appliances > 50,000 Btuh (15 kW)

K = Clearance to a mechanical air supply inlet

6 feet (1.83 m)

3 feet (91 cm) above if within 10 feet (3 m)
horizontally

L = Clearance above paved sidewalk or paved

driveway located on public property

7 feet (2.13 m) †

*

M = Clearance under veranda, porch deck, or

balcony

12 inches (30 cm) ‡

*

Figure 15. Vent Termination Clearances for Direct Vent Furnaces